When the alarm type is selected as
Low Alarm,
first contact output opens after an on-delay time
(L
ON DEL)
if the measured voltage becomes less than the entered minimum voltage value
(LOW
VALUE)
and immediate opening option is inactive. In this case, down segment on the LCD and the
dot in the C1 segment turn on. When the measured voltage rises above the set minimum value
(LOW
VALUE)
as much as the low hysteresis value
(LOW HYS)
and immediate opening option is inactive,
first output contact closes after an off-delay time
(L OFF DEL)
. In this case, down segment on the
LCD and the dot in the C1 segment turn off.
When the alarm type is selected as
High-Low Alarm (Range)
,
LOW VALUE
operates as low alarm
and
HGH VALUE
operates as high alarm. While this alarm type is selected, minimum voltage value
(
LOW VALUE)
cant be entered higher than maximum voltage value
(HGH VALUE)
.
HIGH ALARM
HGH VALUE
The highest value that you want the measured voltage to reach is entered in this menu. A value between
-200 and 200 can be entered. If the value is entered as 0 (zero), high alarm is deactivated.
When the alarm type is selected as
High Alarm,
first contact output opens after an on-delay time
(H
ON DEL)
if the measured voltage becomes more than the entered maximum voltage value
(HGH
VALUE)
and immediate opening option is inactive. In this case, up segment on the LCD and the dot
in the C1 segment turn on. When the measured voltage drops below the set maximum value
(HGH
VALUE)
as much as the high hysteresis value
(HIGH HYS)
and immediate opening option is inactive,
first output contact closes after an off-delay time
(H OFF DEL)
. In this case, up segment on the LCD
and the dot in the C1 segment turn off.
HIGH HYS
Return value (to the normal operation) from the high voltage fault which is the hysteresis voltage value
is entered in this menu. A value between 0 and 100 can be entered.
H ON DEL
It is the delay time for the high voltage alarm to activate. The value is entered as seconds. It can be
entered between 000.0 and 999.9 seconds.