ENFORCER Delayed Egress Timer 

 

 

SECO-LARM U.S.A., Inc                                                                                      7

 

SECO-LARM U.S.A., Inc.                                                                                                   

               33                                              

7                                                                                         

 

 

 

Lock Status Jumper: 

 

When the lock status jumper is ON, the lock status 
input will detect whether the door is closed and will 

trigger relock functions. 

 

The lock status input may be bypassed in order to 

keep the door unlocked for an indefinite period of time 
without activating the remote alarm output. 

 

To bypass the lock status input, set jumper 1 to OFF. 

 

The lock status input must be ON for BOCA Mode 
(See pg. 5, 

Relock Modes

). 

Jumper 1 

Jumper 2 

Jumper 3 

Default: OFF 

Default: OFF 

 

The SA-025EQ is equipped with a 500mA@12VDC 

transistor ground output for a local alarm, typically an 
audible or visual device. 

 

The local alarm output can be set for steady or 
pulsing. When set ON, the local alarm pulses during 

the pre-delay, gradually pulsing faster until the end of 
the pre-delay time. The local alarm will continue 
signaling steady 5 seconds after the lock has been 
released. When set OFF, the local alarm is steady 
during the pre-delay time and for 5 seconds after the 

lock has been released. 

 

LED 4 is on when the local alarm output is active. 

 

The local alarm signals when the pre-delay bypass  
is used (see pg. 9). 

 

To set the local alarm output type ON (steady) or 

OFF (pulsing), use jumper 3 on the right side of the 
circuit board. 

Local Alarm Output Type Jumper: 

Security Mode Jumper: 

 

To activate security mode, set jumper 2 to ON. 

 

In security mode, after the initiate device (such as a 
push-to-exit bar) has been triggered and the  

pre-delay timer has ended, the lock will remain active 
until the initiate device has been triggered a second 
time. 

 

When security mode is OFF, the initiate device must 

only be activated once. 

 

Default: OFF 

Summary of Contents for ENFORCER SA-025EQ

Page 1: ...lay outputs for lock relay and remote alarm Transistor ground output for local alarm outputs Auto or programmed relocking after power loss IMPORTANT Users and installers of this product are responsibl...

Page 2: ...put Form C 10A 24VDC Local alarm output transistor ground 500mA 12VDC Door status input Status LEDs show relay status Bypass input immediately releases locks Free egress input allows easy egress durin...

Page 3: ...er see pg 6 Post delay timer potentiometer see pg 6 Terminal block see pg 4 LED 1 Blue If ON the SA 025EQ is being powered see pg 9 LED 2 Red If ON the lock relay is energized see pg 8 LED 3 Red If ON...

Page 4: ...holes located on the side of the unit to a mounting surface Normally energized Screen print refers to energized state as normal Remote alarm relay output 10A 24VDC Form C Relay NO NC COM see pg 8 Loc...

Page 5: ...relocked by a reset device connected to the Reset Input For information on connecting a reset device see pg 4 Wiring Diagram This reset device is often a momentary spring loaded key switch BOCA Mode T...

Page 6: ...h at the bottom right of the circuit board Power Up Mode DIP Switch 1 There are two types of power up modes These modes determine the relocking status in case of a power loss Programmed Relock DIP Swi...

Page 7: ...al alarm pulses during the pre delay gradually pulsing faster until the end of the pre delay time The local alarm will continue signaling steady 5 seconds after the lock has been released When set OFF...

Page 8: ...e pg 7 LED 4 red is on when the local alarm output is active Lock Relay Output The SA 025EQ is equipped with a 10A 24VDC Form C dry relay output that can be used with a fail safe or fail secure lock T...

Page 9: ...e bypass input is used to bypass the SA 025EQ and allow unrestricted entry and exit via the door When the bypass input is activated the lock will immediately release It will remain released until the...

Page 10: ...ted to the reset input This device will manually reset the lock 4 A spring loaded switch is connected to the pre delay bypass input This will allow any authorized user immediate access to the protecte...

Page 11: ...mon terminal is connected to a positive voltage and the normally closed terminal is connected to the SA 025EQ s initiate input 3 An audible indicator sounds during the pre delay time to alert the user...

Page 12: ...rkmanship The sole obligation of SECO LARM and the purchaser s exclusive remedy shall be limited to replacement or repair only at SECO LARM s option In no event shall SECO LARM be liable for any speci...

Reviews: