ENFORCER Delayed Egress Timer 

 

8

 

                                                        

SECO-LARM U.S.A., Inc.

 

 

 

 

 

 

 

 

 

 

 

Remote Alarm Relay Output: 

 

The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output for a  
remote alarm. 

 

The remote alarm relay is normally energized. The onboard screen print refers to the 
energized state as normal. 

 

A remote alarm connected to this output will begin signaling at the start of the  
pre-delay timer. 

 

The remote alarm will continue signaling until the door is relocked. 

 

In the event of power loss, the remote alarm relay will de-energize to trigger the  

remote alarm. 

 

The remote alarm will signal when the pre-delay bypass is activated. 

 

The remote alarm will also signal during free egress if the door is left open longer than  

5 seconds (door status jumper must be ON for this to occur). 

 

LED 3 (red) is on when the remote alarm relay is energized. 

Local Alarm Output: 

 

The SA-025EQ is equipped with a 500mA@12VDC transistor ground output for a  

local alarm. 

 

The local alarm output can be set for steady or pulsing by changing jumper 3 (see pg. 7) 

 

LED 4 (red) is on when the local alarm output is active. 

Lock Relay Output: 

 

The SA-025EQ is equipped with a 10A@24VDC Form C dry relay output that can be used 

with a fail-safe or fail-secure lock. 

 

The lock relay is normally energized. The onboard screen print refers to the energized state 

as normal. 

 

In standard mode, the lock relay will de-energize after the pre-delay time expires. The lock 
relay will re-energize when the reset input is activated. 

 

In BOCA mode, the lock relay will de-energize after the pre-delay time expires. The lock 
relay will re-energize after a door with a N.C. magnetic contact attached to the lock status 

input has been closed for 30 consecutive seconds. 

 

In timed mode, the lock relay will de-energize after the pre-delay time expires. The lock 

relay will re-energize after the post-delay time expires. 

 

LED 2 (red) is on when the lock relay is energized. 

Pre-Delay Bypass Input (N.O.+): 

 

Connect a N.O. switch between the pre-delay bypass and the positive terminal. 

 

The pre-delay bypass input bypasses the pre-delay time for immediate egress. 

 

The remote alarm and local alarm outputs are still active when the pre-delay bypass is used. 

 

The door will relock according to the relock mode. 

Summary of Contents for ENFORCER SA-025EQ

Page 1: ...lay outputs for lock relay and remote alarm Transistor ground output for local alarm outputs Auto or programmed relocking after power loss IMPORTANT Users and installers of this product are responsibl...

Page 2: ...put Form C 10A 24VDC Local alarm output transistor ground 500mA 12VDC Door status input Status LEDs show relay status Bypass input immediately releases locks Free egress input allows easy egress durin...

Page 3: ...er see pg 6 Post delay timer potentiometer see pg 6 Terminal block see pg 4 LED 1 Blue If ON the SA 025EQ is being powered see pg 9 LED 2 Red If ON the lock relay is energized see pg 8 LED 3 Red If ON...

Page 4: ...holes located on the side of the unit to a mounting surface Normally energized Screen print refers to energized state as normal Remote alarm relay output 10A 24VDC Form C Relay NO NC COM see pg 8 Loc...

Page 5: ...relocked by a reset device connected to the Reset Input For information on connecting a reset device see pg 4 Wiring Diagram This reset device is often a momentary spring loaded key switch BOCA Mode T...

Page 6: ...h at the bottom right of the circuit board Power Up Mode DIP Switch 1 There are two types of power up modes These modes determine the relocking status in case of a power loss Programmed Relock DIP Swi...

Page 7: ...al alarm pulses during the pre delay gradually pulsing faster until the end of the pre delay time The local alarm will continue signaling steady 5 seconds after the lock has been released When set OFF...

Page 8: ...e pg 7 LED 4 red is on when the local alarm output is active Lock Relay Output The SA 025EQ is equipped with a 10A 24VDC Form C dry relay output that can be used with a fail safe or fail secure lock T...

Page 9: ...e bypass input is used to bypass the SA 025EQ and allow unrestricted entry and exit via the door When the bypass input is activated the lock will immediately release It will remain released until the...

Page 10: ...ted to the reset input This device will manually reset the lock 4 A spring loaded switch is connected to the pre delay bypass input This will allow any authorized user immediate access to the protecte...

Page 11: ...mon terminal is connected to a positive voltage and the normally closed terminal is connected to the SA 025EQ s initiate input 3 An audible indicator sounds during the pre delay time to alert the user...

Page 12: ...rkmanship The sole obligation of SECO LARM and the purchaser s exclusive remedy shall be limited to replacement or repair only at SECO LARM s option In no event shall SECO LARM be liable for any speci...

Reviews: