29
Operation
13.Then, press OK button to start grid S V_min test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
14.After grid S V_min test is over, the LCD will show the result and “(OK) to start F_max”, and
the inverter will reconnect automatically.
15.Then, press OK button to start grid S F_max test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
16.After grid S F_max test is over, the LCD will show the result and “(OK) to start F_min”, and
the inverter will reconnect automatically.
17.Then, press OK button to start grid S F_min test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
18.After grid S F_min test is over, the LCD will show the result and “(OK) to start Grid T V_max”,
and the inverter will reconnect automatically.
19.Then, press OK button to start grid T V_max test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
20.After grid T V_max test is over, the LCD will show the result and “(OK) to start V_min”, and
the inverter will reconnect automatically.
21.Then, press OK button to start grid T V_min test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
22.After grid T V_min test is over, the LCD will show the result and “(OK) to start F_max”, and
the inverter will reconnect automatically.
23.Then, press OK button to start grid T F_max test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.
24.After grid T F_max test is over, the LCD will show the result and “(OK) to start F_min”, and
the inverter will reconnect automatically.
25.Then, press OK button to start grid T F_min test. Alternatively press ESC button to exit from
“New Autotest”. If there is no button operation within 5 seconds, the test will start automatically. If
the test has started, key operation is invalid untill this test is over.