19
PE
N
L3 L2 L1 10mm
Figure 11 AC output area with terminal block for 5 wires of cable
Below is the AC cable specification table when select the cable for installation.
Model
Cable (Cu)
Micro-Breaker
25A
25A
32A
32A
≥4mm
2
≥4mm
2
≥6mm
2
≥6mm
2
Table 4 Cable and Micro-breaker Requirement
Note:
For safety reasons, make sure you select the correct specification cables for installation,
otherwise the power will make the cable hot and overload, it could result in death or serious injury.
Below are the steps for AC output wiring.
Step1:
Get out of the four screws at four corners of the cover, get off the cover.
Step2:
There are 5 white terminals, which are PE, N, L3(T), L2(S), L1(R). Put the 5 wire of AC cable
through the house tunnel, then put the wire into the terminals correctly(make sure the phase
sequence is correctly connected
)
.
Step3:
After 5 wires are connected with terminals please check the wire is in right location.
(L wire is connected with L terminal)
Step4:
Put the terminal house on the terminals, get four screws on.
RCMU breaker should be installed between inverter and grid, and its rated fault current:
100 mA≤Ifn≤300 mA
,
0.1S
,
Any load should not be connected with inverter directly.
Installation
SolarLake
10000TL
SolarLake
12000TL
SolarLake
15000TL
SolarLake
17000TL