Commands and functions
P.
216 of 349
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
1
1
0
0
0
0
0*128 + 1*64 + 1*32 + 0*16 + 0*8 + 0*4 + 0*2 + 0*1
U16
112
Figure 6: Physically Addressing of an Actor with 1/3/5
●
date1 .. data18
of data type u08
Depending on the
Controlfield
the first two bytes e.g. contain the command to run, and in
most cases the information to be transmitted.
●
For an available commands, please refer to the literature.
Effect
The state of the input objects are copied to an KNX Telegram object. The individual address of the
sender can not be given, as It will be set to the address of the bus access unit (= interface connected
to the Enertex ® EibPC).
Data type result (Return)
●
none
Example: physical Addressing
Every 10 minutes a read request is to be sent to the actuator with the physical address of 1/3/5
if cycle(10,0) then eibtelegramm(188u08,4869u16,112u08,0u08) endif
// you could also use hex-values
//if cycle(10,0) then eibtelegramm(0xbc,0x1105u16,0x70,0x00) endif
HandbuchEibPC_USA-30.odt, 2017-05-11
Enertex
®
Bayern GmbH - Erlachstraße 13 - 91301 Forchheim - [email protected]