^SynOhrMultiSenseKNX-Eng-13.odt, 2014-05-06 Page 30 of 49
ID
Function
Name
Length
Type
Flags
168 Measured Value
Noise Level
1 byte
[non-standard]
--CT--
In this object is written the measured noise level when the parameterized noise level is exceeded.
Licenses:
Premium
ID
Function
Name
Length
Type
Flags
169 on/off
Energy Saving Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
With this object the room controller can be put into sleep mode. The display and the lighting will be deactivated.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
170 Display
Display-Text 21
14 bytes
(c14)
[16.0]
DPT_String_ASCII
-WC---
About this and the next object a 28 characters text can be sent to the room controller in order to output it in the dot
matrix area of the display. For text length that do not fit in the line of the display scrolling is enabled. The display
appears as soon as the object 171 is received.
Licenses:
Premium
ID
Function
Name
Length
Type
Flags
171 Display
Display-Text 22
14 bytes
(c14)
[16.0]
DPT_String_ASCII
-WC---
See object 170.
Lizenzen:
Premium
ID
Function
Name
Length
Type
Flags
172 Measured Value
(external)
Temperature for the Display
16 bits
(f16)
[9.1]
DPT_Value_Temp
-WCTU-
To this object the current temperature from an external sensor can be sent to the room controller to show it on the
display. See under parameter „Display → Numeric Display - ...“ the value
External Sensor
.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
173 Audio Output
Confirmation Command
1 bit (b01)
[1.1] DPT_Switch
-WC---
Via this object the confirmation tone for the command can be enabled and disabled.
0 = Deactivated Command Tone
1 = Activated Command Tone
Note:
The read value of the object is only defined if the object at least was written once.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
174 Audio Output
Threshold for Level
8 bits (u08) [non-standard]
-WC---
This object defines the threshold of the noise level in dB, at its exceeding a value is sent (see object ID 168)
respectively on the display for a cycle time of change is shown (during this the dB-Symbol is active).
Note:
The read value of the object is only defined if the object at least was written once.
Licenses:
Premium
ID
Function
Name
Length
Type
Flags
175 Audio Output
Threshold for Noise Level active
1 bit (b01)
[1.1] DPT_Switch
-WC---
Via this object the threshold for noise level display can be activated and deactivated. Only with activated threshold a
value is sent or shown on the display.
0 = Threshold deactivated
1 = Threshold activated
Note:
The read value of the object is only defined if the object at least was written once.
Licenses:
Premium
Enertex
®