^SynOhrMultiSenseKNX-Eng-13.odt, 2014-05-06 Page 23 of 49
ID
Function
Name
Length
Type
Flags
6
on/off
Status of the Coolingactor
1 bit (b01)
[1.1] DPT_Switch
R-CT--
This object specifies whether to be cooled. Telegrams are sent automatically when the state changes.
The object value is 1 if the „coolingactor (analog)“ > 0.
The object value is 0 if the coolingactor (analog)“ = 0.
For example the message can be used for controlling a flow pump.
Note:
This object is only available if the parameter „General → Heating / Cooling“ is set on
Cooling, Cooling (2-
stage), Heating and Cooling respectively Heating and Cooling (2-stage)
.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
7
Setpoint
Add. Heatingactor (analog)
8 bits (u08) [5.1] DPT_Scaling
--CT--
This object gives out the setpoint for the additional heatingactor by linear control.
Note:
This object is only available if the parameter „General → Heating / Cooling“ is set on
Heating (2-stage)
respectively Heating and Cooling (2-stage).
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
8
on/off
Status of the additional Heatingactors
1 bit (b01)
[1.1] DPT_Switch
--CT--
This object specifies whether to be heated. Telegrams are sent automatically when the state changes.
The object value is 1 if object „Add. Heatingactor (analog)“ > 0.
The object value is 0 if object „Add. Heatingactor (analog)“ = 0.
For example the message can be used for controlling a flow pump.
Note:
This object is only available if the parameter „General → Heating / Cooling“ is set on
Heating (2-stage)
respectively Heating and Cooling (2-stage).
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
9
Setpoint
Add. Coolingactor (analog)
8 bits (u08) [5.1] DPT_Scaling
--CT--
This object gives out the setpoint for the additional coolingactor by linear control.
Note:
This is only available if the parameter „General → Heating / Cooling“ is set on
Cooling (2-stage) respectively
Heating and Cooling (2-stage).
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
10
on/off
Status of the additional Coolingactors
1 bit (b01)
[1.1] DPT_Switch
--CT--
This object specifies whether to be cooled. Telegrams are sent automatically when the state changes.
The object is 1 if object „Add. Coolingactor (analog)“ > 0.
The object is 0 if object „Add. Coolingactor (analog)“ = 0.
For example the message can be used for controlling a flow pump.
Note:
This object is only available if the parameter „General → Heating / Cooling“ is set on
Cooling (2-stage)
respectively Heating and Cooling (2-stage).
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
11
Choice
Operating Mode of the Controller
8 bite (u08) [20.102]
DPT_HVACMode
RWCT--
For the operating modes comfort, standby, night- and building-protection exists a common 1 byte change over. While
running time the operating mode switching can be done after receiving a single telegram. The operating mode is
determined by the following values.
0 = Automatic
1 = Comfort
2 = Standby
3 = Night
4 = Building Protection
Note:
This object is only available if the parameter „General → Operating mode specified via“ is set on
Byte-Object
.
Licenses:
Starter, Standard, Premium
Enertex
®