^SynOhrMultiSenseKNX-Eng-13.odt, 2014-05-06 Page 24 of 49
ID
Function
Name
Length
Type
Flags
12
on/off
Comfort Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
This object can be switched to the „Comfort“ mode. Thus the current setpoint temperature is set to the basic setpoint
temperature. The telegram can be triggered e.g. by presence detector or a presence button.
Note:
This object is only avaible if the parameter „General → Operating mode specified via“ is set to 1 bit object.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
13
on/off
Standby-Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
This object can be switched to the „Standby“ mode. Thus the current setpoint temperature is lowered in the heating
mode minus the configurable standby-reduction. In the cooling mode the current setpoint temperature is raised to the
basic setpoint temperature plus the standby-raising. The telegram can be triggered e.g. by a timer.
Note:
This object is only available if the parameter „General → Operating mode specified via“ is set on
1-bit-object.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
14
on/off
Night Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
This object can be switched to the „Night“ mode. Thus the current setpoint temperature is lowered in the heating
mode to the basic setpoint temperature minus the configurable night-reduction. In the cooling mode the current
setpoint temperature is raised to the basic setpoint temperature plus the night-raising. The telegram can be triggered
e.g. by a timer.
Note:
This object is only available if the parameter „General → Operating mode specified via“ is set on
1-bit-objects.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
15
on/off
Building Protection Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
This object can be switched over to the „Building Protection“ mode. Thus the temperature should not fall below the
configurable setpoint frost protection respectively in the cooling mode should not exceed the configurable setpoint
heat protection.
If the parameter is „General → Use Door- or Window-Contact“ is set on
Yes
the building protection mode can
automatically activated, if a monitored door or a monitored window are opened. This occurs the immediate closing of
the heating and cooling valve. On the one hand the waste of heating or cooling energy is avoide on the other hand is
ensured that the temperature controller remains active and the room does not freeze or and heat up any.
Note:
This object is only available if the parameter „General → Operating mode specifies via“ is set on
1-bit-objects
.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
16
on/off
Dew-Point Mode
1 bit (b01)
[1.1] DPT_Switch
-WC---
This object can be switched over to the „Dew-Point“ mode. Thus the heating or cooling is turned off unconditionally.
Note:
This object is only available if the parameter „General → Operating mode specifies via“ is set on
1-bit-objects.
Licenses:
Starter, Standard, Premium
ID
Function
Name
Length
Type
Flags
17
Status
Controller Status
8 bits (u08) [non-standard]
R-CT--
This object contains the current controller status that is automatically sent when the status changes. The controller
status adds the following values:
1 = Comfort
2 = Standby
4 = Night
8 = Building Protection
16 = Dew Point
32 = Heating
64 = Dead Zone (Controller inactive)
128 = Frost Alarm
Licenses:
Starter, Standard, Premium
Enertex
®
Bayern GmbH – Ebermannstädter Straße 8 - 91301 Forchheim - [email protected]