Figure 18: Existing ventilation
unit with natural gas heating
before installation of the Luba GL
collector system
Figure 19: Modified system with
lateral solar damper (on left) and
bypass damper (in front). Both
motors and protective covers are
visible from the exterior
3.13 Connecting the collectors to the exterior ventilation ducts
The collectors can be joined to the ventilation ducts allowing the transport of hot air towards the
ventilation unit.
Ventilation ducts with acoustic insulation applied to their interior is recommended. It is also
possible to paint the ducts black. The absence of insulation or black paint is not recommended
but is not critical to the system’s performance.
Figure 20: Connection to the ventilation ducts
Table 7 : Dimensions and selection of the connection to the ventilation ducts
Air flow of the row
L/s (CFM)
Part #
Diameter
125 to 285 (265 to 600)
La-130-12
300mm (12’’)
286 to 565 (601 to 1200)
La-130-16
400mm (16’’)
566 to 1040 (1201 to 2200)
La-130-20
500mm (20’’)