Topclean S
6 Commissioning
Hauser
89
• Clean Int:
This programme for interval cleaning is permanently assigned to one function. Cleaning times and
repeat cycles are freely adjustable.
You can select and configure Clean Int. only within the "Automatic" control type.
Note that the cleaning times, repeat cycles, etc. that you set here are taken over for all weekdays
and for the Clean programme.
Interval cleaning allows you to define cleaning intervals for a given period of time (max. 1 day).
In practical life, two different operating modes are used, interval measuring and interval cleaning:
– In case of interval cleaning, the sensor is mainly in measuring position. It is cleaned at specified
intervals.
– In case of interval measuring, the sensor is mainly in service position (aggressive media). It is
moved into the process into measuring position at specified intervals. If the sensor remains in
service position for a long time, i.e. you have defined a long integral action time, set the "Air"
to 0 sec to prevent the sensor from drying in.
Examples for programme sequences
C07-CPC300xx-05-06-00-en-008.eps
ƒig. 46:
Example for the programme sequence of "Clean C" and "Clean Int".
• Clean Int runs from 08:00 ... 12:00 at an interval (programme time + measuring time + integral
action time) of 10 minutes.
This means cleaning is started every 10 minutes: 08:00, 08:10, etc.
The last cycle is started at 11:50.
• Clean Int runs from 08:00 ... 11:00 at an interval of 50 minutes.
This means cleaning is started every 50 minutes: 08:00, 08:50, 09:40.
The last cycle is started at 09:40. The cycle due at 10:30 cannot be started because it would be
finished after the set end time at 11:20.
Clean C
Hold
Hold and after-effect time
Prog.
Cleaning / calibration
Cleaning / integral action time
Cleaning / integral action time
Clean Int
Hold
Hold and after-effect time
Hold and after-effect time
Measuring time
Measuring
time
Interval
Prog.
Summary of Contents for Topclean S CPC30
Page 154: ...10 Technical data Topclean S 154 Endress Hauser...
Page 156: ...11 Appendix Topclean S 156 Endress Hauser C07 CPC30xxx 19 06 08 en 006 eps...
Page 157: ...Topclean S 11 Appendix Endress Hauser 157 C07 CPC30xxx 19 06 08 en 007 eps...
Page 158: ...11 Appendix Topclean S 158 Endress Hauser C07 CPC30xxx 19 06 08 en 008 eps...
Page 159: ...Topclean S 11 Appendix Endress Hauser 159...
Page 160: ...11 Appendix Topclean S 160 Endress Hauser C07 CPC30xxx 19 06 08 en 002 eps...
Page 161: ...Topclean S 11 Appendix Endress Hauser 161 C07 CPC30xxx 19 06 08 en 003 eps...
Page 162: ...11 Appendix Topclean S 162 Endress Hauser C07 CPC30xxx 19 06 08 en 014 eps...
Page 163: ...Topclean S 11 Appendix Endress Hauser 163 C07 CPC30xxx 19 06 08 en 015 eps...
Page 164: ...11 Appendix Topclean S 164 Endress Hauser C07 CPC30xxx 19 06 08 en 011 eps...
Page 165: ...Topclean S 11 Appendix Endress Hauser 165 C07 CPC300xx 19 06 08 en 010 eps...
Page 166: ...11 Appendix Topclean S 166 Endress Hauser C07 CPC30xxx 19 06 08 en 012 eps...
Page 167: ...Topclean S 11 Appendix Endress Hauser 167 C07 CPC30xxx 19 06 08 en 013 eps...
Page 176: ...Index Topclean S 176 Endress Hauser...
Page 178: ...www endress com worldwide BA236C 07 en 11 04 51504339 Printed in Germany FM SGML 6 0 DT...