Installation
6.1
Mounting requirements
6.1.1
Mounting position
Mounting location
h
A0032998
4
Mounting location
Ideally, the sensor should be installed in an ascending pipe, while ensuring a sufficient
distance is kept to the next pipe elbow: h ≥ 5 × DN.
Orientation Teqwave I
A0035457
5
Orientation of Teqwave I
Mount Teqwave I so that the active sensor area can be fully immersed in the measured
liquid.
If installing the sensor in a pipe, make sure the sensor is aligned correctly to avoid
irregular flow to the sensor. Rotate the sensor so that the dot on the process connection is
aligned with the flow direction.
If installing the sensor in a horizontal position, make sure the sensor is aligned correctly to
avoid the buildup of deposits around the sensing element. Rotate the sensor so that the
black dot on the process connection points up or down.