Operating options
Teqwave F/I Modbus TCP
28
Hauser
6. Settings menu → "Network settings" → "Gateway"
7. Settings menu → "Network settings" → "DHCP"
Navigation using the Viewer
1. Menu "Teqwave Transmitter" → "Network settings" → "IP address"
2. Menu "Teqwave Transmitter" → "Network settings" → "Subnet mask"
3. Menu "Teqwave Transmitter" → "Network settings" → "Gateway"
4. Menu "Teqwave Transmitter" → "Network settings" → "Switch DHCP status"
The operating tool communicates the settings to the transmitter as soon as the "Send
(parameters)" button is clicked.
Parameter overview with brief description
Parameter
Description
Selection/entry/display
Factory setting
Network status
(transmitter)
Displays the current
connection status.
• Static IP address
• DHCP
• Not connected
-
System name
(transmitter)
Enter the name or
NetBIOS name of the
transmitter where it can
be reached in the
network.
Any sequence of letters
and characters, max. 15
characters.
LSC
[transmitter serial
number]
MAC address
(transmitter)
Displays the physical
network address of the
device.
Byte-wise notation, colon-
separated
Depends on the
transmitter
IP address
Enter the IP address.
• The transmitter
IP address
assigned at the
factory is
indicated on the
transmitter
nameplate.
• The network
settings of the
computer must be
configured with a
static IP address
in the same
address range.
Character string with the
following format:
192.168.1.xyz
192.168.1.212
Subnet mask
Use one of the predefined
values for the subnet
mask of the transmitter or
enter a new value.
• 255.255.255.0
• 255.255.0.0
• 255.0.0.0
• Character string with
the following format:
w.x.y.z
255.255.255.0