Operation
Tankvision Gauge Link
32
Hauser
Example 7
A system requires to be connected to 5 of SAAB rosemount gauges address 01 - 05.
Level and temperature are required.
Host baud rate is 9600, with a parity of none.
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
1100=82(return)
Gauge type is a RADAR (82)
1=2(return)
Level address = 2 (modbus address = 2)
1101=82(return)
Gauge type is a RADAR (82)
2=3(return)
Level address = 3 (modbus address = 3)
1102=83(return)
Gauge type is a SERVO (83)
3=4(return)
Level address = 4 (modbus address = 4)
1103=83(return)
Gauge type is a SERVO (83)
(return)
Enter
Result
HTS=9600(return)
HPA=N(return)
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
100=1(return)
Temp address = 1
1=2(return)
Level address = 2 (modbus address = 2)
101=2(return)
Temp address = 2
2=3(return)
Level address = 3 (modbus address = 3)
102=3(return)
Temp address = 3
3=4(return)
Level address = 4 (modbus address = 4)
103=4(return)
Temp address = 4
4=5(return)
Level address = 5 (modbus address = 5)
104=5(return)
Temp address = 5
(return)
Enter
Result