Tankvision Gauge Link
Operation
Hauser
31
Level and temperature are required from all gauges.
Host baud rate is 9600, with a parity of none. BPM baud rate is 1200.
Example 6
A system requires to be connected to 2 of 873 gauges and 2 off 854 gauges with address 01
– 04.
Level only is requires.
Host baud rate is 9600, with a parity of none. BPM baud rate is 1200.
Enter
Result
FTS=1200(return)
HTS=9600(return)
HPA=N(return)
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
100=1(return)
Temp address = 1
1100=82(return)
Gauge type is a RADAR (82)
1=2(return)
Level address = 2 (modbus address = 2)
101=2(return)
Temp address = 2
1101=82(return)
Gauge type is a RADAR (82)
2=3(return)
Level address = 3 (modbus address = 3)
102=3(return)
Temp address = 3
1102=82(return)
Gauge type is a RADAR (82)
3=4(return)
Level address = 4 (modbus address = 4)
103=4(return)
Temp address = 4
1103=82(return)
Gauge type is a RADAR (82)
4=5(return)
Level address = 5 (modbus address = 5)
104=5(return)
Temp address = 5
1104=83(return)
Gauge type is a SERVO (83)
5=6(return)
Level address = 6 (modbus address = 6)
105=6(return)
Temp address = 6
1105=83(return)
Gauge type is a SERVO (83)
(return)
Enter
Result
FTS=1200(return)
HTS=9600(return)
HPA=N(return)