Operation
Tankvision Gauge Link
30
Hauser
Example 4
A system requires to be connected to 4 of NRF590 gauges (emulating Enraf GPU) with
address 01 – 04.
Level Only is required.
Host baud rate is 9600, with a parity of none. BPM baud rate is 1200.
Example 5
A system requires to be connected to 4 of 873 gauges and 2 off 854 gauges with address 01
– 06.
3=4(return)
Level address = 4 (modbus address = 4)
103=4(return)
Temp address = 4
1103=78(return)
Gauge type is a NRF590 (78)
4=5(return)
Level address = 5 (modbus address = 5)
104=5(return)
Temp address = 5
1104=78(return)
Gauge type is a NRF590 (78)
5=6(return)
Level address = 6 (modbus address = 6)
105=6(return)
Temp address = 6
1105=78(return)
Gauge type is a NRF590 (78)
(return)
Enter
Result
FTS=1200(return)
HTS=9600(return)
HPA=N(return)
CONFIG(return)
Enable configuration
0=1(return)
Level address = 1 (modbus address = 1)
1100=78(return)
Gauge type is a NRF590 (78)
1=2(return)
Level address = 2 (modbus address = 2)
1101=78(return)
Gauge type is a NRF590 (78)
2=3(return)
Level address = 3 (modbus address = 3)
1102=78(return)
Gauge type is a NRF590 (78)
3=4(return)
Level address = 4 (modbus address = 4)
1103=78(return)
Gauge type is a NRF590 (78)
(return)
Enter
Result