Installation
Proline Prowirl 73
6
Hauser
2
Installation
2.1
Transporting to the measuring point
• Transport the measuring device to the measuring point in the original packaging.
• The covers or caps fitted to the process connections prevent mechanical damage to the sensors
during transportation and storage. For this reason, do not remove the covers or caps until
immediately before installation.
2.2
Installation conditions
It is advisable to support heavy sensors for mechanical reasons (to protect the piping).
2.2.1 Dimensions
For the dimensions of the measuring device, see the associated Technical Information on the
CD-ROM.
2.2.2 Mounting location
A0008731
To transport the unit, use slings slung around the process
connections or use lugs (if available).
#
Warning!
Risk of injury! The device can slip.
The center of gravity of the measuring device may be
higher than the holding points of the slings.
Always ensure that the device cannot slip or turn around
its axis.
A0008732
Do not lift measuring devices by the transmitter housing
or the connection housing in the case of the remote
version. Do not use chains as they could damage the
housing.
A0008733
• Recommended minimum distance in all directions (A):
100 mm (3.94 in)
• Required cable length (L):
L + 150 mm (5.91 in)
L
A