Proline Prowirl 73

Installation

Hauser

9

2.2.5 Inlet and outlet runs

The following inlet and outlet runs must be taken into account. The longest inlet run shown 
must be observed if two or more flow disturbances are present.

A0001867

Perforated plate flow conditioner

A specially designed perforated plate flow conditioner, available from Hauser, can be 
installed if it is not possible to observe the inlet runs required. The flow conditioner is fitted 
between two piping flanges and centered with the mounting bolts. Generally, this reduces the 
inlet run required to 10 × DN with complete accuracy.

A0001887

A = Inlet run
B = Outlet run

1 = Reduction
2 = Extension
3 = 90° elbow or T-section

4 = 2 × 90° elbow, three-dimensional 
5 = 2 × 90° elbow
6 = Control valve

15 x DN

5 x DN

A

1

3

5

2

4

6

A

A

A

A

A

B

B

B

B

B

B

17 x DN + 8 x h

5 x DN

20 x DN

5 x DN

40 x DN

5 x DN

25 x DN

5 x DN

50 x DN

5 x DN

h

8 x DN

2 x DN

5 x DN

Summary of Contents for Proline Prowirl 73

Page 1: ...in the Operating Instructions and the additional documentation on the CD ROM supplied Depending on the device version the complete device documentation consists of Brief Operating Instructions this d...

Page 2: ...Post installation 10 2 4 Post installation check 13 3 Wiring 14 3 1 Connecting the various housing types 15 3 2 Special points to note when connecting the transmitter 17 3 3 Degree of protection 18 3...

Page 3: ...Proline Prowirl 73 Table of contents Endress Hauser 3...

Page 4: ...measuring device should only be installed in a de energized state Repairs may only be performed if a genuine spare parts kit is available and this repair work is expressly permitted If performing weld...

Page 5: ...essure instruments Measuring devices for use in systems that need to be monitored are labeled accordingly on the nameplate Relevant national regulations must be observed when using these devices The d...

Page 6: ...For the dimensions of the measuring device see the associated Technical Information on the CD ROM 2 2 2 Mounting location A0008731 To transport the unit use slings slung around the process connection...

Page 7: ...raphic orientation A There is vertical downward flow in the pipe in this orientation it must be ensured that the measuring tube is always completely full In order to ensure that the maximum permissibl...

Page 8: ...from overheating or undercooling The maximum permitted insulation level is indicated in the following graphic 1 flanged version 2 wafer version These apply equally to both the compact version and the...

Page 9: ...Hauser can be installed if it is not possible to observe the inlet runs required The flow conditioner is fitted between two piping flanges and centered with the mounting bolts Generally this reduces t...

Page 10: ...lease ensure there is a large enough distance between the device and the measuring point so there are no negative effects on vortex formation in the sensor A0003780 2 2 6 Vibrations The correct operat...

Page 11: ...e measuring tube and piping Seals projecting into the flow current have a negative effect on the vortex formation after the bluff body and cause inaccurate measurement The direction of the arrow on th...

Page 12: ...direction to the stop Note There are recesses in the rotating groove at 90 stages only compact version These help you align the transmitter more easily c Retighten the lock screw A0003237 a Unscrew co...

Page 13: ...is mounted to a warm pipe make sure that the housing temperature does not exceed the maximum permissible value Standard 40 to 80 C 40 to 176 F EEx d version 40 to 60 C 40 to 140 F ATEX II 1 2 GD versi...

Page 14: ...nected transmitter the same Are the measuring point number and labeling correct visual inspection Correct internal diameter and correct surface roughness quality Sensor orientation correctly selected...

Page 15: ...number The remote version must be grounded In doing so the sensor and transmitter must be connected to the same potential matching Observe the cable specifications of the connecting cable Operating I...

Page 16: ...de the cover 3 1 1 Compact version Ex i non Ex Connection compartment Ex i non Ex transmitter housing A0008737 Transmitter connection 1 2 3 Connection diagram in the electronics compartment Connecting...

Page 17: ...cover Cable gland for connecting cable Cable gland for optional output for HART version Terminal connector for connecting cable Terminal connector for optional output for HART version A0008744 Transmi...

Page 18: ...0003784 A Fieldbus cable B Ground terminal Between the stripped fieldbus cable and the ground terminal the cable shielding should not exceed a length of 5 mm 0 20 in C Terminal connector D Ground term...

Page 19: ...rain relief and are they routed securely Is the cable type route completely isolated Without loops and crossovers Are all of the screw terminals correctly tightened Are all the cable entries installed...

Page 20: ...associated Operating Instructions on the CD ROM Note No hardware settings are needed for measuring devices with HART and FOUNDATION Fieldbus type communication 4 1 Device address Has to be set for me...

Page 21: ...lay module from the retaining rails and refit onto the right retaining rail with the left side this secures the display module d Fold up the plastic cover e Fold up the cover of the I O board COM modu...

Page 22: ...power up checks and device self checks As this procedure progresses the following messages can appear on the onsite display The measuring device starts operating as soon as the startup procedure is co...

Page 23: ...units 48 25 xx yy 3702 6 x 1 2 3 4 A0007559 Operating keys 1 Minus key for entering selecting 2 Plus key for entering selecting 3 Enter key for calling the function matrix saving When the keys are pr...

Page 24: ...n A0007562 1 F Enter the function matrix starting with measured value display 2 P Select the group e g OPERATION F Confirm selection 3 N Select function e g LANGUAGE 4 P Enter code 73 only for the fir...

Page 25: ...OMMISSIONING function appears 4 Intermediate step if configuration is blocked P Enter the code 73 confirm with F and thus enable configuration 5 P Go to Commissioning Quick Setup 6 P Select YES F Conf...

Page 26: ...100 value line 2 Current output all parameters Frequency output all parameters Process parameter all relevant parameters Language Fluid 1 5 QS Commisioning Language Select Fluid Saturated steam Gas vo...

Page 27: ...XTERNAL TEMPERATURE SENSOR REQUIRED When SATURATED STEAM DELTA HEAT or WATER DELTA HEAT is selected the HART INPUT function is set to TEMPERATURE automatically Select Fluid Compressed air Superheated...

Page 28: ...sign current Selection frequency Selection pulse Selection status QS Commisioning Current range Value 4 mA Assign frequency Assign pulse Assign status Value 20 mA End value frequency Pulse value Switc...

Page 29: ...rm the fluid selected in this function and configure all the subsequent functions of the FLOW COMPUTER group If reading in pressure using the HART input functionality please program the respective fun...

Page 30: ...etting 126 The device address can be configured via Miniature switches see Hardware settings 20 Device functions Operating program FieldCare see Operating Instructions on the CD ROM 5 6 Troubleshootin...

Page 31: ...Proline Prowirl 73 Commissioning Endress Hauser 31...

Page 32: ...KA00031D 06 EN 14 11 71154544 FM SGML 9 0...

Reviews: