Description of device functions
Proline Prosonic Flow 91
84
Hauser
10.7
Group TOTALIZER
Functional description TOTALIZER
SUM
The total for the totalizer's measured variable aggregated since measuring commenced
appears on the display.
This value can be positive or negative, depending on:
• Flow direction
and/or
• Setting in the MEASURING MODE function
Display
:
Max. 6-digit floating-point number, incl. sign and unit (e.g. 15467.4 m
3
)
!
Note!
• The totalizer's response to faults is defined in the central "FAILSAFE MODE" function
• The unit of the totalizer is defined in the UNIT VOLUME function
OVERFLOW
The total for the totalizer's overflow aggregated since measuring commenced appears on
the display.
Total flow quantity is represented by a floating-point number consisting of max. 6 digits.
You can use this function to view higher numerical values (>9,999,999) as overflows. The
effective quantity is thus the total of the OVERFLOW function plus the value displayed in
the SUM function.
Example:
Reading for 2 overflows: 2 E7 dm
3
(= 20,000,000 dm
3
)
The value displayed in the function "SUM" = 196,845 dm
3
Effective total quantity = 20,196,845 dm
3
Display
:
Integer with exponent, including sign and unit, e.g. 2 E7 dm
3
RESET TOTALIZER
Use this function to reset the sum and the overflow of the totalizer to "zero" (= RESET).
Options
:
NO
YES
Factory setting
:
NO