Commissioning
Proline Promass E 100 Modbus RS485
56
Hauser
10.3.5 Configuring the partial filled pipe detection
The
Partially filled pipe detection
submenu contains parameters that have to be set for
configuring empty pipe detection.
Navigation path
"Setup" menu → Partial filled pipe detection
Structure of the submenu
Partially filled pipe detection
→
Assign process variable
Low value partial filled pipe detection
High value partial filled pipe detection
Response time part. filled pipe detect.
Parameter overview with brief description
Parameter
Prerequisite
Description
Selection/
User entry
Factory setting
Assign process
variable
–
Select a process variable to
detect empty or partially
filled pipes.
• Off
• Density
• Reference
density
Density
Low value
partial filled
pipe detection
One of the following
options is selected in the
Assign process variable
parameter:
• Density
• Reference density
Enter a lower limit value to
activate detection of an
empty or partially filled
pipe.
Max. 15-digit,
positive floating-
point number
Country-
dependent:
• 0.2 kg/l
• 12.5 lb/cf
High value
partial filled
pipe detection
One of the following
options is selected in the
Assign process variable
parameter:
• Density
• Reference density
Enter an upper limit value
to activate detection of an
empty or partially filled
pipe.
Max. 15-digit,
positive floating-
point number
Country-
dependent:
• 6 kg/l
• 374.6 lb/cf
Response time
part. filled pipe
detect.
One of the following
options is selected in the
Assign process variable
parameter:
• Density
• Reference density
Enter the time interval
until the diagnostic
message
S862 Partly
filled pipe detection
is
displayed for an empty or
partially filled pipe.
0 to 100 s
1 s