Proline Promass E 100 Modbus RS485
Commissioning
Hauser
53
10.3.3 Configuring communication interface
The
Communication
submenu guides you systematically through all parameters that must
be configured for selecting and setting the communication interface.
Navigation path
"Setup" menu → Communication
Structure of the submenu
Communication
→
Bus address
Baud rate
Data transfer mode
Parity
Byte order
Assign diagnostic behavior
Failure mode
Parameter overview with brief description
Parameter
Description
Selection/
User entry
Factory setting
Bus address
Enter device address.
1 to 247
247
Baud rate
Define data transfer
speed.
Baud rate list box
19
200 BAUD
Data transfer mode
Select data transfer mode. • ASCII
Transmission of data in
the form of readable
ASCII characters. Error
protection via LRC.
• RTU
Transmission of data in
binary form. Error
protection via CRC16.
RTU
Parity
Select parity bits.
ASCII picklist
• 0 = even
• 1 = odd
RTU picklist
• 0 = even
• 1 = odd
• 2 = no parity bit/1 stop
bit
• 3 = no parity bit/2 stop
bits
Even
Byte order
Select byte transmission
sequence.
• 0-1-2-3
• 3-2-1-0
• 1-0-3-2
• 2-3-0-1
1-0-3-2