5 Operation
Hauser
43
5.5.3
Display of error messages
Type of error
Errors that occur during commissioning or measuring are displayed immediately on the local dis-
play. If two or more system or process errors occur, the error with the highest priority is the one
shown on the display.
The measuring system distinguishes between two types of error:
•
System error:
This group includes all device errors, for example communication errors, hardware
errors, etc.
•
Process error:
This group includes all application errors, e.g. fluid not homogeneous, etc.
a0001211
Fig. 27:
Error messages on the display (example)
1
Error type: P = process error, S = system error
2
Error message type:
$
= fault message, ! = notice message
3
Error designation: e.g. FLUID INHOM. = fluid is not homogeneous
4
Error number: e.g. # 702
5
Duration of most recent error occurrence (in hours, minutes and seconds)
Error message type
The flowmeter assigns system error and process error to two error message types (fault message or
notice message) in accordance with a predefined algorithm and classifies them accordingly
Page 72 ff.
Serious system errors, e.g. module defects, are always identified and classed as “fault messages” by
the measuring device.
Notice message (!)
• The error in question has no effect on measurement currently in progress.
• Displayed as
→
Exclamation mark (!), error type (S: system error, P: process error).
• Presentation on the FOUNDATION Fieldbus
→
Notice messages are transmitted to subsequent
function blocks or higher-level process control systems by means of the status “UNCERTAIN” of
the output value OUT (AI Block).
Fault message (
$
)
• The error in question interrupts or stops measurement currently in progress.
• Displayed as
→
Lightning flash
(
$
),
error designation (S: system error, P: process error).
• Presentation on the FOUNDATION Fieldbus
→
Fault messages are transmitted to subsequent
function blocks or higher-level process control systems by means of the status “BAD” of the out-
put value OUT (AI Block).
1
2
4
5
3
+24.502
X X X X X X X X X X
# 0 0 0 0 0 : 0 0 : 0 5
P
+24.502
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Page 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...