6 Commissioning
Proline Promass 83 FOUNDATION Fieldbus
46
Hauser
6.2
Commissioning
Note the following points:
• The files required for commissioning and network configuration can be obtained as described on
• The device is identified by the FOUNDATION Fieldbus in the host or configuration system via
the device ID (DEVICE_ID). The DEVICE_ID is a combination of the manufacturer ID, device
type and device serial number. It is unique and can never be duplicated. The DEVICE_ID of the
Promass 83 is composed as follows:
DEVICE_ID = 452B481051-XXXXXXXXXXX
452B48 = Hauser
1051 = Promass 83
XXXXXXXXXXX = device serial number (11-digit)
6.2.1
Commissioning
The following description allows step-by-step commissioning of the measuring device and all the
necessary configuration for the FOUNDATION Fieldbus:
1.
Switch on the Measuring Device.
2.
Note the DEVICE_ID on the device nameplate (see Page 9).
3.
Open the configuration program.
4.
Load the device description file or CFF file into the host system or into the configuration pro-
gram. Ensure you use the correct system files. Refer to the example on Page 36.
The first time it is connected Promass 83 reports as follows:
– E+H_PROMASS_83_ xxxxxxxxxxx (Tag name PD-TAG)
– 452B481051- xxxxxxxxxxx (Device_ID)
– Block structure:
!
Note!
The Promass 83 is supplied with the bus address “250” and is thus in the address range reser-
ved for readdressing of field devices, between 248 and 251. This means that the LAS (Link
Active Scheduler) automatically assigns the device a free bus address in the initialization phase.
Display text (xxx... = serial number)
Base index
Description
RESOURCE_ xxxxxxxxxxx
258
Resource Block
TRANSDUCER_xxxxxxxxxxx
1100
Transducer Block
ANALOG_INPUT_1_ xxxxxxxxxxx
350
Analog Input Funktionsblock 1
ANALOG_INPUT_2_ xxxxxxxxxxx
390
Analog Input Funktionsblock 2
ANALOG_INPUT_3_ xxxxxxxxxxx
430
Analog Input Funktionsblock 3
ANALOG_INPUT_4_ xxxxxxxxxxx
470
Analog Input Funktionsblock 4
ANALOG_INPUT_5_ xxxxxxxxxxx
510
Analog Input Funktionsblock 5
ANALOG_INPUT_6_ xxxxxxxxxxx
550
Analog Input Funktionsblock 6
ANALOG_INPUT_7_ xxxxxxxxxxx
590
Analog Input Funktionsblock 7
DISCRETE_OUTPUT_ xxxxxxxxxxx
780
Discrete Output Funktionsblock
PID_ xxxxxxxxxxx
810
PID Funktionsblock
Summary of Contents for Proline Promass 83
Page 24: ...3 Installation Proline Promass 83 FOUNDATION Fieldbus 24 Endress Hauser ...
Page 34: ...4 Wiring Proline Promass 83 FOUNDATION Fieldbus 34 Endress Hauser ...
Page 64: ...6 Commissioning Proline Promass 83 FOUNDATION Fieldbus 64 Endress Hauser ...
Page 66: ...7 Maintenance Proline Promass 83 FOUNDATION Fieldbus 66 Endress Hauser ...
Page 90: ...9 Trouble shooting Proline Promass 83 FOUNDATION Fieldbus 90 Endress Hauser ...
Page 116: ...Index Proline Promass 83 FOUNDATION Fieldbus 116 Endress Hauser ...
Page 118: ...www endress com worldwide BA065D 06 en 12 04 50098623 FM SGML 6 0 ...