3 Installation
PROline Promag 23
16
Hauser
3.2.4
Inlet and outlet runs
If possible, install the sensor well clear of fittings such as valves, T-pieces, elbows, etc.
Compliance with the following requirements for the inlet and outlet runs is necessary in
order to ensure measuring accuracy:
Inlet run
5 x DN
Outlet run
2 x DN
Fig. 10:
Inlet and outlet runs
3.2.5
Vibrations
Secure the piping and the sensor if vibration is severe.
"
Caution:
Information on resistance to vibration and shock can be found on
Fig. 11:
Measures to prevent vibration of the measuring device
F06-2x