Operation
Through analysis of the signal strength over a longer period of time (also in conjunction
with minimum and maximum values in function
2510
), the following conclusions may be
drawn:
Display
Analysis
Usable detection
range
Min Max
The limit level detection is adjusted reasonably well:
• In this case, the usable detection range generally equals the
preset detection range.
• The current output can put out almost the whole possible
range (in this case about 5.7 to 19.5 mA).
Usable detection
range
The limit level detection is overdriven:
• In this case, the usable detection range equals only a small
portion of the preset upper detection range.
• The current output can put out only a narrow upper range
(in this case about 17.2 to 20.0 mA) of the total possible
range.
Usable detection
range
The limit level detection is underdriven:
• In this case, the usable detection range equals only about
half of the preset lower detection range.
• The current output can put out only half of the lower range
(in this case about 4.0 to 12.3 mA) of the total possible
range.
In case of a substantial over- or underdrive, the boundaries of the detection range should
be moved accordingly.
• Manual adjustment LL in function
2112
→
28
• Manual adjustment UL in function
2113
→
29
If there is no opportunity for analysis of the signal strength over an extended period
of time, minimum and maximum values can be used (→
46).
9�3�2 Signal strength motion (2M)
Application
2000
→
Application analysis
2500
→
Signal strength motion
2550
This function is used to display the current signal strength of the motion detection (2M)
depending on the performed setup (function
2122
→ 30 and function
2123
→
31).