8�4�2�5 4 mA value of the magnify
Application
2000
→
Current output
2300
→
4mA value
2320
This function is used to enter the percentage value for the lower limit (4 mA) while the
magnify is enabled (function
2310
).
Options: 0 to 100 %
8�4�2�6 20 mA value of the magnify
Application
2000
→
Current output
2300
→
20mA value
2330
This function is used to enter the percentage value for the upper limit (20 mA) while the
magnify is enabled (function
2310
).
Options: 0 to 100 %
The 4 mA value (function
2310
) must always be lower than the 20 mA value; if it is not,
an error message is displayed.
8�4�2�7 Current output in failure mode
Application
2000
→
Current output
2300
→
Failure mode
2340
This function is used to define the failure mode of the current output.
Options: "MIN (<4mA)", "MAX (>20mA)", "Fixed value"
[mA] [mA]
110%
-10%
22
3.6
110%
-10%
22
3.6
t
t
[mA]
110%
-10%
22
Function 2350
3.6
$
$
$
t
24 Behavior of the current output in failure mode