Commissioning
8.4.2.1 Switching contact 1 assignment
Application
2000
→
Assignment outputs
2200
→ Switching output 1
2210
This function is used to assign switching contact 1 (relay or SSR) to measuring channel 1
(limit, 1M), measuring channel 2 (motion, 2M) or the fault state.
Options: "Limit (1M)", "Motion (2M)", "Fault"
The option for the second measuring channel (bulk flow detection, 2M) is only available
for the corresponding device versions.
8.4.2.2 Switching contact 2 assignment
Application
2000
→
Assignment outputs
2200
→ Switching output 2
2220
This function is used to assign switching contact 2 (relay or SSR) to measuring channel 1
(limit, 1M), measuring channel 2 (motion, 2M) or the fault state.
Options: "Limit (1M)", "Motion (2M)", "Fault"
• The switching output 2 is only available for the corresponding device versions.
• The option for the second measuring channel (bulk flow detection, 2M) is only available
for the corresponding device versions.
8�4�2�3 Current output assignment
Application
2000
→
Assignment outputs
2200
→
Current output
2230
This function is used to assign the current output to measuring channel 1 (limit, 1M) or
measuring channel 2 (motion, 2M).
Options: "Limit (1M)", "Motion (2M)"
The option for the second measuring channel (bulk flow detection, 2M) is only available
for the corresponding device versions.
8�4�2�4 Current output mode
Application
2000
→
Current output
2300
→
Current output mode
2310
This function can be used to switch on output magnify. For this function, a small segment
of the 0-100 % detection range is shown on the current output of 4-20 mA.
Options: "Standard", "Magnify"
Magnify
Standard
4mA
20mA
4mA
Function
2320
20mA
Function
2330
082
23 Current output mode