Liquitrend QMW43
Description of Device Parameters
Hauser
33
Navigation
Application → Sensor → Offset buildup
Description
The parameter displays the value that was last suppressed by the device in the "Calibrate
buildup zero (GTZ)" parameter. Alternatively, a manually defined value for signal
suppression can also be entered here.
Input range
0 to 9.0 mA
Get DC-Media
Navigation
Application → Sensor → Get DC-Media
Note
This function can only be used with media conductivity values ≥ 5 µS/cm. The system must
be filled completely to use this function.
Description
This function determines the current dielectric constant of the medium present. The value
determined for the dielectric constant is communicated to the DC-Media parameter.
Current Output 2 (OU2)
Lower Range Value for 4 mA (LRV)
Upper Range Value for 20 mA (URV)
Navigation
Application → Current Output 2 (OU2) → Lower Range Value for 4 mA (LRV)
Application → Current Output 2 (OU2) → Upper Range Value for 20 mA (URV)
Note
The configured measuring range for buildup is always = 0 to 10. The parameter is
therefore not displayed in this case. The configured measuring range for conductivity can
be changed.
The span can be ordered as a preset value in the product structure via order code 570
"Service", option HT "Configuration output 1 + output 2".
Description
For specifying the measuring range for the current output.
Input range:
Minimum span:
0 to 110
000.0
1
000.0
Switch on value
Last configured value.
Frequency Output 2 (OU2)
Lower Range Value for 300 Hz (LRV)
Upper Range Value for 3000 Hz (URV)
Navigation
Application → Frequency Output 2 (OU2) → Lower Range Value for 300 Hz (LRV)
Application → Frequency Output 2 (OU2) → Upper Range Value for 3000 Hz (URV)