Liquiphant FTL64
Commissioning
Hauser
39
8.2.2
FEL62 switching behavior and signaling
YE
YE
GN
RD
GN
RD
1.
2.
>1 s
3.
MAX
MIN
(L-)
<100 µA
3
1
L+
(L-)
3
1
L+
ΔU
I
L
(L-)
A
3
1
L+
(L-)
3
1
L+
<100 µA
(L-)
3
1
L+
<100 µA
(L-)
3
1
L+
<100 µA
K
K
K
K
K
K
A0039211
36
FEL62 switching behavior and signaling
A
After the test button is pressed, the DC-PNP output is switched off for at least 10 s (I < 100 µA) even if the
button is pressed for < 10 s. If the test button is pressed for > 10 s, the DC-PNP output remains switched off
(I < 100 µA) until the test button is released. The DC-PNP output is then switched on again.
8.2.3
FEL64, FEL64DC switching behavior and signaling
1.
2.
>1 s
3.
MAX
MIN
YE
GN
RD
YE
GN
RD
3 4 5
6 7 8
3 4 5
6 7 8
3 4 5
6 7 8
3 4 5
6 7 8
3 4 5
6 7 8
3 4 5
6 7 8
A
A0039212
37
FEL64, FEL64DC switching behavior and signaling
A
After the test button is pressed, the relay is de-energized for at least 10 s even if the button is pressed for <
10 s. If the test button is pressed for > 10 s, the relay remains de-energized until the test button is released.
The relay is then energized again.
8.2.4
FEL67 switching behavior and signaling
A distinction must be made between MAX and MIN operating modes in the case of
the FEL67 electronic insert!