Liquiphant FTL64
Electrical connection
Hauser
21
Power consumption
P ≤ 0.5 W
Current consumption
I ≤ 10 mA (without load)
The red LED flashes in the event of an overload or short-circuit. Check for an overload or
short-circuit every 5 s.
Load current
I ≤ 350 mA with overload and short-circuit protection
Capacitance load
C ≤ 0.5 µF at 55 V, C ≤ 1.0 µF at 24 V
Residual current
I < 100 µA (for blocked transistor)
Residual voltage
U < 3 V (for switched through transistor)
Behavior of output signal
• OK status: switched through
• Demand mode: blocked
• Alarm: blocked
Terminals
Terminals for cable cross-section up to 2.5 mm
2
(14 AWG). Use ferrules for the wires.
Overvoltage protection
Overvoltage category II