Commissioning
Gammapilot M FMG60 PROFIBUS PA
68
Hauser
"Avg. pulse rate" (*11)
A0018118
Initially, the pulse rate strongly fluctuates. In the course of time an average value is reached.
If the value is sufficiently stable, the function can be left by pressing "E".
Thereafter, the Gammapilot M changes to the
"calibration" (*15)
function. Select
"stop/
edit"
to stop the averaging procedure. The value is then automatically transmitted to the
"full calibr." (*16)
or
"empty calibr." (*18)
function respectively.
NOTICE
Avg. Pulse rate
‣
The maximum integration time is 1000 s. The value is then transmitted automatically to
the
"full calibr." (*16)
or
"empty calibr." (*18)
function.
‣
The integration is
not
terminated by pressing "E" in the
"avg. pulse rate" (*11)
function.
It is continued until the selection of
"stop/edit"
in the
"calibration" (*15)
function. This
may result in a slight deviation between the last displayed average pulse rate and the
final
"full calibr." (*16)
or
"empty calibr. (*18)
.
"Full calibration" (*16) / "Empty calibration" (*18)
On-site display
Meaning
avg. pulse rate
*11
The average pulse rate is displayed in this function (after
selection of "start" in the previous function). Initially, this value
fluctuates (because of the decay statistics), but due to the
integration it reaches an average value in the course of time.
The longer the averaging is performed the lower are the
remaining fluctuations.
2548 cps
c/s
t
"
E
"
On-site display
Meaning
full calibr.
*16
The pulse rate of the respective calibration points is displayed
in these functions. The displayed value must be confirmed by
pressing "E".
"-1"
indicates, that no background calibration is
present yet. In this case there are two options:
• either return to the "calibration" (*15) function and restart
the calibration
• or enter a knwon or calculated pulse rate (manual
calibration)
33 cps
empty calibr.
*18
2548 cps