Deltabar M PMD55 FOUNDATION Fieldbus
Commissioning
Hauser
21
Position adjustment
007 Operation
4 Cancel
Use to exit the edit mode for the parameter.
Confirm
8
Commissioning
The device is configured for the "Pressure" measuring mode as standard.
The measuring range and the unit in which the measured value is transmitted correspond to
the data on the nameplate.
L
WARNING
The permitted process pressure is exceeded!
Risk of injury if parts burst! Warnings are displayed if the pressure is too high.
‣
If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in
succession (depending on the setting in the "Alarm behavior" (050) parameter): "S140
Working range P" or "F140 Working range P" "S841 Sensor range" or "F841 Sensor range"
"S971 Adjustment"
‣
Only use the device within the sensor range limits!
NOTICE
The permitted process pressure is undershot!
Messages are displayed if the pressure is too low.
‣
If a pressure smaller than the minimum permitted pressure or greater than the maximum
permitted pressure is present at the device, the following messages are output in
succession (depending on the setting in the "Alarm behavior" (050) parameter): "S140
Working range P" or "F140 Working range P" "S841 Sensor range" or "F841 Sensor range"
"S971 Adjustment"
‣
Only use the device within the sensor range limits!
8.1
Commissioning with an operating menu
8.1.1
Selecting the language, measuring mode and pressure unit
Language (000)
Navigation
Main menu → Language
Write permission
Operator/Maintenance/Expert
Description
Select the menu language for the local display.