Operation options
Deltabar M PMD55 FOUNDATION Fieldbus
16
Hauser
Function of the operating elements
Key
Meaning
Zero
pressed for at least 3
seconds
Position adjustment
Press key for at least 3 seconds. The LED on the electronic insert lights up briefly if
the pressure applied has been accepted for position adjustment. See also the
following Section "Performing position adjustment on site.''
Zero
pressed for at least 12
seconds
Reset
All the parameters are reset to the order configuration.
Performing position adjustment on site
• Operation must be unlocked.
• The device is configured for the "Pressure" measuring mode (Cerabar, Deltabar) or "Level"
measuring mode (Deltapilot) as standard.
Operation via FF configuration program: In the Pressure Transducer Block, you can change
the measuring mode by means of the PRIMARY_VALUE_TYPE parameter.
• The pressure applied must be within the nominal pressure limits of the sensor. See
information on the nameplate.
• To reconcile the parameter database, perform a "Reconcile device" (after position
adjustment) with the FF host.
Perform position adjustment:
1. Pressure is present at the device.
2. Press key for at least 3 seconds.
3. If the LED on the electronic insert lights up briefly, the pressure applied has been
accepted for position adjustment. If the LED does not light up, the pressure applied was
not accepted. Observe the input limits. For error messages see the Operating
Instructions.