Deltabar M PMD55 FOUNDATION Fieldbus
Mounting
Hauser
7
5
Mounting
5.1
Mounting requirements
5.2
Installing the
NOTICE
Incorrect handling!
Damage of the device!
‣
Disassembly of the screws with item number (1) is not permissible under any
circumstances and will result in loss of warranty.
1
A0024166
5.2.1
Orientation
• Due to the orientation of the Deltabar M, there may be a shift in the measured value, i.e.
when the container is empty, the measured value does not display zero. You may correct
this zero point shift by a position adjustment in one of the following ways:
• Via the keys on the electronics module (→ 16, "Function of the operating elements")
• Via the operating menu (, "Position adjustment")
• Refer to the relevant national or international standards for general recommendations on
laying the piping.
• Using a three-valve or five-valve manifold allows for easy commissioning, installation and
maintenance without interrupting the process.
• When routing the impulse piping outdoors, ensure that sufficient anti-freeze protection is
used, e.g. by using pipe heat tracing.
• Lay the piping with a monotonic gradient of at least 10 %.
• Hauser offers a mounting bracket for mounting on pipes or walls (, "Wall and pipe
mounting (optional)").
Installation position for flow measurement
Flow measurement in gases
Mount the Deltabar M above the measuring point so that the condensate which may be
present, can run off into the process piping.