Description of device parameters
Ceraphant PTC31B, PTP31B, PTP33B IO-Link
68
Hauser
Navigation
Display: EF → Switching delay.../Switchback delay...
IO-Link: Parameter → Application → Switch output (OU1) → Switching delay.../Switchback
delay...
Description
To prevent switch-on and switch-off if values are around the switch point "SP1" or the
switchback point "RP1", a delay in a range of 0 – 50 seconds, to two decimal places, can be
set for the individual points.
If the measured value leaves the switching range during the delay time, the delay time
starts again from scratch.
Example
• SP1 = 2 bar (29 psi)
• RP1 = 1 bar (14.5 psi)
• dS1 = 5 seconds
• dR1 = 2 seconds
dS1/: ≥2 bar (29 psi) must be present for at least 5 seconds for SP1 to become active.
dR1/: ≥1 bar (14.5 psi) must be present for at least 2 seconds for RP1 to become active.
2
1
0
SP1
RP1
dS1
dS1
dR1
0
HNO
p
t
1
HNC
A0034027
0
0-signal. Output open in quiescent state.
1
1-signal. Output closed in quiescent state.
2
Hysteresis (difference between the value of the switch point "SP1" and the value of the switchback point "RP1")
HNO NO contact
HNC NC contact
SP1 Switch point 1
RP1 Switchback point 1
dS1 Set time for which the specific switch point must be reached continuously without interruption until an
electrical signal change takes place.
dR1 Set time for which the specific switchback point must be reached continuously without interruption until an
electrical signal change takes place.
Input range
0.00 - 50.00 seconds
Factory setting
0
Switching delay time, output 2 (dS2)
Switchback delay time, output 2 (dR2)