Ceraphant PTC31B, PTP31B, PTP33B IO-Link
Installation
Hauser
17
Type
Process isolating
diaphragm axis is
horizontal (A)
Process isolating diaphragm
pointing upwards (B)
Process isolating diaphragm
pointing downwards (C)
PTP31B
PTP33B
Calibration position, no
effect
Up to +4 mbar (+0.058 psi)
Up to –4 mbar (–0.058 psi)
PTC31B
< 1 bar (15 psi)
Calibration position, no
effect
Up to
+0.3 mbar (+0.0044 psi)
Up to
–0.3 mbar (–0.0044 psi)
PTC31B
≥1 bar (15 psi)
Calibration position, no
effect
Up to +3 mbar (+0.0435 psi)
Up to –3 mbar (–0.0435 psi)
A position-dependent zero shift can be corrected on the device .
5.4
Mounting location
5.4.1
Pressure measurement
Pressure measurement in gases
Mount the device with shutoff device above the tapping point so that any condensate can
flow into the process.
1
2
A0025920
1
Device
2
Shutoff device
Pressure measurement in vapors
For pressure measurement in vapors, use a siphon. The siphon reduces the temperature to
almost ambient temperature. Preferably mount the device with the shutoff device and
siphon below the tapping point.
Advantage:
• defined water column causes only minor/negligible measuring errors and
• only minor/negligible heat effects on the device.
Mounting above the tapping point is also permitted.
Note the max. permitted ambient temperature of the transmitter!
Take the influence of the hydrostatic water column into consideration.