Programmes:
Creating and changeover
210
Sampling
Progr. 1
Time/
Quantity/
Event
211
Time interval
Progr. 1
Range:
00h 01min.
...99h 59 min.
212
Sampling
quantity
Progr. 1
Litre or m
3
0001...9999
213
Sample
distribution
Progr. 1
Change on
Time or
Samples or
ext. Signal
214
Fill time per
bottle
Progr. 1
Range:
00h 01min.
...99h 59min
215
Samples per
bottle
Progr. 1
0001...9999
220
Progr. 2
Works setting:
Time
221
Progr. 2
Works setting:
10 min
222
Progr. 2
Works setting:
-
223
Progr. 2
Works setting:
To time
224
Progr. 2
Works setting:
1 hour
225
Progr. 2
Works setting:
-
230
Progr. 3
Works setting:
Time
231
Progr. 3
Works setting:
1 hour
232
Progr. 3
Works setting:
-
233
Progr. 3
Works setting:
To time
234
Progr. 3
Works setting:
24 hours
235
Progr. 3
Works setting:
-
240
Progr. 4
Works setting:
Quantity
241
Progr. 4
Works setting:
-
242
Progr. 4
Works setting:
10 m
3
243
Progr. 4
Works setting:
To time
244
Progr. 4
Works setting:
2 hours
245
Progr. 4
Works setting:
-
250
Progr. 5
Works setting:
Quantity
251
Progr. 5
Works setting:
-
252
Progr. 5
Works setting:
10 m
3
253
Progr. 5
Works setting:
To time
254
Progr. 5
Works setting:
2 hours
255
Progr. 5
Works setting:
-
260
Progr. 6
Works setting:
Event
261
Progr. 6
Works setting:
-
262
Progr. 6
Works setting:
10 m
3
263
Progr. 6
Works setting:
To samples
264
Progr. 6
Works setting:
-
265
Progr. 6
Works setting:
1
270
Programme
change
criteria
Time
Quantity:Too
much/little.
Ext.Signal.
Not active
271
Programme
change
from A to B
Act.Progr.#X
to
Target progr.
#1...6
272
Programme
change
,
Switch times
Times:
Change to.
change back.
273
Programme
change
Day selection
Daily the same
To:Mo...Sun
Back:Mo...Sun
274
Programme
change
Changeover
value
I/Sec or m
3
/h
1...999
275
Change to
next bottle
on:
Change to.
change back.
276
Sample
after
programme
change
Yes / No
280
Overfill
security
Yes / No
Operation and display
asp-port d 2 se
28