Front Rail Rear Rail
Step 3: Adjust the rear slider plate on the Outer Sliding rails to increase or decrease the length
of the rails to properly fit the cabinet.
Step 4: Attach the Outer Sliding Rails (stationary) to the cabinet front mounting rails using 2
screws on each side of the rail. These screws will be placed in the middle two holes. The outer
two holes will be where the AC6000 is mounted.
NOTE: Do not tighten completely as they may need to be adjusted for the width of the AC6000
●
AC6000 screw
●
Outer Slide Rails screw
●
Outer Slide Rails screw
●
AC6000 screw
*Above is the order for which the screws will be installed.
Step 5: With the rails at the proper length, install 2 cage nuts and 2 screws at the rear of the
cabinet to fasten the stationary rail to the cabinet. Place the screws at the top and bottom of
the 4 holes.
Step 6: With two people, lift the AC6000 unit into the cabinet by inserting the sliding rails on the
UPS (AC6000) into the track of the stationary Outer Slide rails. Approximately
⅓
of the way in
you will hear a click. This is the latch engaging which disables the rail from being completely
pulled out. When fully seated install the remaining 4 screws into the cage nuts to secure the
unit in the rack.
To remove the AC6000 remove the mounting screws on each side, and slide the unit out. When
the latches are exposed activate them while continuing to slide the unit out of the
4.5
Field Wiring
●
To wire the unit in the field, ensure that the electrical service is properly rated for
the desired output.