Electrical Power Connectors
Standard:
Input: NEMA L6-30R (24A input)
Output: NEMA L6-30P
Optional:
For 6kW output on 50A service:
Option 1
– CS8265/4
Option 2
– Hardwire I/O
(Intended for loads in excess of 5kW to
accommodate full power at low line conditions.)
Option 3
– For Europe, 24A input using 332C6/P6.
Note: User must include upstream branch protection. For
standard configuration and option 3, branch protection must
not exceed 30 A. For Options 1 & 2, branch protection must
not exceed 50 A.
Table 3-1: AC6000 Technical Specifications