●
Use stranded copper conductors rated to a minimum of 300 VAC and 90°C
between 5.26-13.3 mm
²
.
●
See Table 4.5-1 below for wiring requirements based upon available service and
desired power output levels.
Location Wire Name
30A Service (24A max)
50A Service (37A max)
Input
Input Line 1 (pos 3)
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Input Line 2 (pos 4)
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Output*
Output Line 1 (pos 1)
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Output Line 2 (pos 2)
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Safety
Ground**
Input Safety Ground
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Output Safety Ground
Min. 5.26 mm2 (10AWG)
Min. 13.3 mm2 (6AWG)
Table 4.5-1: Field Wiring Table
*For hard-wired solution, user must provide a mechanical disconnect between the
AC6000 output and the load. Mechanical disconnect is NOT provided by Enconnex.
**Attach input safety ground first, secure with M6 nut and affix output safety ground with
second M6 nut last.
For detail on hard-wiring, please see Figure 4.5-1 below.
Figure 4.5-1: Hard-wiring inspection and assembly