Diagnostic test
schedule
8 Days
1-30 Days
Performs a diagnostic test on
the power electronics every
1-30 days. (Intended for
Technician use only)
Min. SOC
Threshold
70%
30%, 40%,
50%, 60%,
70%, 80%,
90%
Sets the battery state of
charge threshold where peak
shaving is no longer
available.
Max. UPS
Power
Supplement
1.0 KW
0.5 KW, 1.0
KW, 1.5 KW,
2.0 KW, 2.5
KW, 3.0 KW
Maximum amount of power
the AC6000 supplies during
peak shave.
Rack Power
Threshold
6 KW
0 KW, 1 KW,
2 KW, 3 KW,
4 KW, 5 KW,
6 KW
Sets the threshold of power
that the server rack pulls
through the AC6000 before
peak shaving is enabled.
Username
admin
User
configurable
Sets the username for
access to the AC6000 web
page.
Password
admin
User
configurable
Sets the password for access
to the AC6000 web page.
Control
Output Cycle
Time
1 sec
1 – 20 sec
Sets the amount of time to
shut the output off when
Cycle Power is selected.
System
Off
Off, On
Turns the system on or off.
Cycle Power
Cycles output power.
Clear Faults
Attempts to clear any fault
conditions on the AC6000.
Table 5.5-2: Parameter Table
5.5.2
SNMP Configuration
The AC6000 has support for SNMP versions 1 through 3. When the AC6000 is configured to
work with SNMPv3, SNMPv1 and v2 SET/GET commands will be ignored. The default
username and password for the SNMPv3 Admin user is Enconnex and ecx@123. The default
username and password for the SNMPv3 Read-Only user is AC6000 and Aes@123. To
configure the AC6000 to work with SNMPv3: