PreHeat Button (1):
When genset doesn’t start in cold weathers, engine can be preheated
with this button. Button function can be set as “button must be held down to preheat” or
“preset preheat time when you press button”. Preheat button can be used in manual mode and
when engine is not running.
Start Button:
This
button is used to start genset . Panel will stop cranking when it detects
engine running signals. Button function can be set as “button must be held down to crank” or
“preset cranking time when you press button”. Start button can be used in manual mode and
when engine is not running. Panel will display “Str” message during cranking.
Stop Button:
This button is used to stop the genset. When you pressed this button first time
panel switched to manual mode and if generator contactor is used before, genset is switched
to cooling mode. If you pressed second time genset stops immediately. Second function of
this button when you press more than 3 seconds panel will switch to off mode.
Generator Contactor (2):
This button is used to transfer load to genset. When genset is
running this button can be used. Led lamp above the button shows contactor status. When the
led lamp is lit, contactor is closed. Generator contactor cannot be closed when the mains
contactor is closed. To close generator contactor, you must open the mains contactor first. In
engine running condition, when you press stop button, generator contactor will open
immediately.