EN-KO Electronic Control Systems                                                                                                      

AMF 4.0/ENG/K.K./02

 

 

8

load. If operator wants to stop the engine in test mode panel must be returned to automatic or 
manual mode. In manual mode you can stop the engine by stop button. 

Manual  Mode:

  If  you press the manual button  genset will be switched to manual mode.  In 

manual mode all start stop and preheat operations, contactor control fulfilled by panel buttons. 

 

PANEL RUNNING PHASES 

 

1.

 

Generator is still: 

In this condition engine running signals must be absent. These are oil 

pressure,  charging  alternator  warning  lamp  signal,  generator  voltage  and  frequency.  In 
manual  mode  panel  doesn’t  react  to  this  signal  but  in  automatic  mode  panel  will  try  to 
stop engine.  If  electricity  panel of genset has manual control and these  are wanted to be 
used. Electronic panel must be switched to manual mode.

 

 
2.

 

Preheating: 

In cold weathers preheating of engine can be necessary. Engine must be still 

during preheating. If parameter “preheating time” is not zero, preheating is accomplished 
before starting process by panel.

 

  
3.

 

Cranking: 

In this stage engine is cranking. All engine signals must be absent and engine 

must be still before cranking. If one of the engine signal is detected before cranking, panel 
switch to start and stop alarm. Panel will show which signal is detected with engine start 
stop  alarm.  If  oil  pressure  signal  is  detected  before  cranking  panel  will  wait  for  it  to 
decrease to zero. If “before cranking oil pressure delay” is elapsed and oil pressure is not 
zero  panel  will  switch  to  start  and  stop  alarm.  In  cranking  stage  all  engine  signals, 
alternator  frequency,  alternator  voltage,  charge  alternator  voltage  and  oil  pressure  is 
controlled.  If  one  of  the  signals  is  detected,  Panel  detects  engine  is  running,  crank 
disconnects  and  switch  to  engine  stabilization  time.  Generator  status  led  starts  to  blink. 
During  cranking,  “Str”  message  is  shown  in  the  display.  Oil  pressure  can  rise  before 
engine  running  so  when  oil  pressure  is  detected,  crank  disconnected  after  “crank 
disconnect oil pressure delay”. 

 

 
4.

 

Stabilization: 

After  generator  running  signals  detected  panel  waits  for  engine  signals  to 

stabilize. After engine stabilization time, all alarms are activated.

 

  
5.

 

Running: 

After stabilization time genset is in running condition. If genset in manual and 

test  modes,  alternator  contactor  time  is  waited  and  alternator  contactor  is  closed.  In 
manual mode operator can close the generator contactor by generator contactor button. In 
running mode generator status led is lit.

 

 
6.

 

Cooling: 

If a stop condition occurs by operator or mains status. Generator is switched to 

cooling period and engine is cooled during “cooling time”. During this time engine status 
led is blinking. If alternator contactor hasn’t been closed since last start cooling period is 
bypassed.  If  mains  failure  occurs  during  cooling  process  generator  is  switched  back  to 
running  mode  and  alternator  contactor  is  closed.  After  cooling  process  generator  is 
switched to stopping condition.

 

 
7.

 

Stopping: 

After cooling stage,  generator switches to stopping stage.  If fueling system is 

operating solenoid, operating solenoid is de-energized. If fueling system is stop solenoid 
solenoid  energizes  until  engine  stops.  If  one  of  the  engine  running  signals  is  detected 
stopping period doesn’t ends. Alternator frequency and voltage, charge alternator warning 
lamp signal and oil pressure must be absent. If panel detects engine signals after “fail to 
stop delay” panel will switch to start stop alarm. 

 

8.

 

Generator shutdown

:

 

Generator is stopped because of a red alarm. Generator cannot be 

started if alarm is not cleared.

  

Summary of Contents for AMF 4.0

Page 1: ...ature and engine hour Generator is monitored constantly and when generator or mains values exceed the limits adjusted in the parameter menu necessary actions are taken and alarm is activated Last ten alarms are recorded in the device memory All operating modes and timings can be adjusted in the parameter menu This flexibility is provided for different kinds of generator applications FUNCTIONS Manu...

Page 2: ...h temperature failure Charge fail warning Low oil pressure failure Periodic service time warning Auxiliary failure AMF 4 0 CONNECTION DIAGRAM AMF 4 0 Generator Contactor Relay Mains Contactor Relay G R S T N U V W N LOAD R S T N GENERATOR MAINS 12 23 19 18 17 22 11 14 35 34 33 32 31 30 29 28 27 26 25 24 Configurable Input 1 Default Oil Pressure Switch Configurable Input 3 Battery 1 2 Oil Pressure ...

Page 3: ...crank or preset cranking time when you press button Start button can be used in manual mode and when engine is not running Panel will display Str message during cranking Stop Button This button is used to stop the genset When you pressed this button first time panel switched to manual mode and if generator contactor is used before genset is switched to cooling mode If you pressed second time gense...

Page 4: ...ilure level to maximum oil press sender level Display Leds These leds are in the right side of numerical displays Leds indicates meaning of the value in the displays Values in the displays can be changed by up down and menu buttons Measuring Mode Button 8 The button selects the displayed values at lower 2 numerical display These displays can show generator voltage and frequency or mains voltage an...

Page 5: ...ons 9 These are manual hand mark automatic A letter and test buttons These buttons set running mode of genset There is mode indication leds near each of these buttons When panel is in off mode you can press these buttons to wake up panel and genset will run in selected mode REAR CONNECTIONS I T I S I R I R I T I S 30 31 32 33 34 35 22 23 24 25 26 27 28 29 G 11 12 13 14 15 16 17 18 19 20 21 CRANKIN...

Page 6: ... Cont NO Output terminal of generator contactor relay This output is connected to generator contactor 15 Charge Fail Excit Warning lamp output of charge alternator must be connected here In the cranking excitation current is supplied to charge alternator over 150 ohm resistor 16 Aux Input 1 Multiple function auxiliary input These inputs are activated if it is connected to battery negative If oil s...

Page 7: ...ator line and neutral are connected to these terminals 30 31 32 33 34 35 Current Transformer Inputs Secondary side of current transformer must be connected here Each transformer must be connected separately Note Battery negative must be connected to earth RUNNING MODES Automatic Mode If you press automatic button marked A genset will switch to automatic mode In this mode panel controls mains volta...

Page 8: ...gnals is detected Panel detects engine is running crank disconnects and switch to engine stabilization time Generator status led starts to blink During cranking Str message is shown in the display Oil pressure can rise before engine running so when oil pressure is detected crank disconnected after crank disconnect oil pressure delay 4 Stabilization After generator running signals detected panel wa...

Page 9: ...his alarm occurs that means panel couldn t start or stop engine All engine signals must be absent and engine must be still before cranking If one of the engine signals is detected before cranking panel switch to start and stop alarm Panel will show which signal is detected with engine start stop alarm If oil pressure signal is detected before cranking panel will wait for it to decrease to zero If ...

Page 10: ...ssword to these sections and enter to these sections by its passwords In parameter section leftmost digit starts to blink If you press up and down buttons you can increase and decrease the value shown in the blinking digit If you want to proceed to digit at one step right menu button must be pressed You can adjust this digit up and down buttons and then you press menu button again If you are in th...

Page 11: ... 9 Mains available 10 Emergency stop 11 Cabinet thermostat alarm 6 P8 Auxiliary input 2 function Same as auxiliary input 1 0 P9 Auxiliary input 3 function Same as auxiliary input 1 10 P10 Auxiliary input 4 function Same as auxiliary input 1 4 P11 Auxiliary input 1 activation method 0 Close to activate 1 Open to activate 0 P12 Auxiliary input 2 activation method Same as auxiliary input 1 0 P13 Auxi...

Page 12: ...password 0 999 060 P45 Analog Oil sender type 0 Analog oil sender disabled 1 Analog Endiksan type 2 Analog Olcusan VDO 7 Bar type 3 Analog Olcusan VDO 10 Bar type 4 Analog Olcusan VDO 80 PSI type 5 Analog VDO 5 Bar 6 Analog AKSA type 6 P46 Oil switch type 0 Oil switch disabled 1 Normally closed for low pressure 2 Normally open for low pressure 0 P47 Low oil pressure level 0 1 9 5 bar 1 2 bar P48 A...

Page 13: ... 9 99 0 87 P80 Generator Vs gain 0 01 9 99 0 87 P81 Generator Vt gain 0 01 9 99 0 87 P82 Generator Ir gain 0 01 9 99 3 53 P83 Generator Is gain 0 01 9 99 3 53 P84 Generator It gain 0 01 9 99 3 53 P85 Battery Voltage gain 0 01 9 99 0 54 P86 Mains Vr offset 29 29 V 0 P87 Mains Vs offset 29 29 V 0 P88 Mains Vt offset 29 29 V 0 P89 Generator Vr offset 29 29 V 0 P90 Generator Vs offset 29 29 V 0 P91 Ge...

Page 14: ...8 2 P62 100 P63 1 P64 98 25 P48 2 P62 100 P63 1 P64 99 26 P48 2 P62 125 P63 1 P64 103 27 P48 2 P62 150 P63 1 P64 144 28 P15 1 P62 100 P53 0 P45 3 P64 17 P48 2 P67 9 P52 1 P68 15 29 P15 1 P62 100 P53 0 P45 3 P64 23 P48 2 P67 9 P52 1 P68 15 30 P15 1 P62 100 P53 0 P45 3 P64 48 P9 10 P48 2 P67 9 P52 1 P68 15 31 P15 1 P62 100 P45 6 P64 51 P48 2 P68 15 P52 1 P67 9 32 P15 1 P62 100 P45 6 P64 65 P48 2 P68...

Page 15: ...ameter selected 1 panel will perform preheating for Preheat time P7 Auxiliary input 1 function It selects function of auxiliary input Auxiliary input can be adjusted as red or yellow alarm Activation time can be always active active from engine starting or active from engine stabilization time When input activates auxiliary input led lit and A1 A2 A3 or A4 message is shown according to activated a...

Page 16: ...Same as auxiliary input 1 P14 Auxiliary input 4 activation method Same as auxiliary input 1 P15 Auxiliary output 1 function This parameter select the functions of auxiliary output 1 Engine running If engine running signal generator voltage frequency or charge alternator warning lamb voltage is detected this output will be activated Panel is in auto or test mode If panel is in automatic or test mod...

Page 17: ...oad transferred to mains P27 Preheat time This parameter defines in automatic preheating how long preheating continues P28 Generator voltage failure delay When generator voltages are out of voltage limits a voltage alarm is given after generator voltage failure delay P29 Generator frequency failure delay When generator frequency is out of frequency limits high low speed alarm is given after genera...

Page 18: ...h input is transferred to analog oil pressure sender input P46 Oil switch type Oil pressure switch type can be selected from this parameter P47 Low oil pressure failure If oil pressure fall below this limit Oil pressure failure alarm is activated P48 Analog temperature sender type Analog coolant temperature sender can be selected from this parameter If genset has only digital coolant temperature s...

Page 19: ...ed all engine running signals absent panel will wait an additional protection delay This is necessary for engine to stop completely before next engine start Do not decrease this value if not necessary P62 Current transformer primary This parameter contains current transformer primary value If Current transformer primary is more than 999 you must change parameter menu current multiplier to x10 mode...

Page 20: ...gain calibration P84 Generator It gain Generator line T current gain calibration P85 Battery Voltage gain Battery voltage gain calibration P86 Mains Vr offset Mains line R voltage offset calibration P87 Mains Vs offset Mains line S voltage offset calibration P88 Mains Vt offset Mains line T voltage offset calibration P89 Generator Vr offset Generator line R voltage offset calibration P90 Generator...

Page 21: ...50VAC 10 A Voltage measurement 20 300VAC Frequency measurement 1 99 Hz Current measurements 5 A current inputs current transformer should be used Connection Screw socket Measurement Accuracy Phase voltages 2 Frequency 0 1Hz Phase currents 2 Charge Excitation Current 80mA 12VDC 160mA 24VDC Housing PPO Polyphenylene oxide 30 Glass Fiber Protection Class IP 52 Front side Weight 600 gr aprox Dimension...

Page 22: ...EN KO Electronic Control Systems AMF 4 0 ENG K K 02 22 Dimensions in mm Specifications are subject to change without notice ...