EN-KO Electronic Control Systems
AMF 4.0/ENG/K.K./02
11
AMF 4.0 PARAMETERS
Initial parameter settings are for genset model 10. These are as following table. For chosen
genset model, parameter table can be loaded by means of parameter 69. Parameters that is
changed according to genset models are specified in the next sections.
No
Parameter
Setting Range
Default Value
Operator Parameters
P0
Operator menu password
0-999
050
P1
Temperature unit
0: Celsius
1: Fahrenheit
0
P2
Crank attempts
1 – 9
3
P3
Cranking time
1-60 sec
10 sec
P4
Cranking pause time
3-60 sec
10 sec
P5
Manuel cranking type
0: Start button must be held down to crank
1: Automatic start
0
P6
Preheating type
0:Preheat button must be hold down to preheat
1: Automatic preheat
0
P7
Auxiliary input 1 function
0: Input disabled
1: Yellow alarm (always active)
2: Yellow alarm (active from starting)
3: Yellow alarm (active form engine stabilization time)
4: Red alarm (always active)
5: Red alarm (active from starting)
6: Red alarm (active from engine stabilization time)
7: Remote start
8: Remote main failure disable
9: Mains available
10: Emergency stop
11: Cabinet thermostat alarm
6
P8
Auxiliary input 2 function
Same as auxiliary input 1
0
P9
Auxiliary input 3 function
Same as auxiliary input 1
10
P10
Auxiliary input 4 function
Same as auxiliary input 1
4
P11
Auxiliary input 1 activation method
0: Close to activate
1: Open to activate
0
P12
Auxiliary input 2 activation method
Same as auxiliary input 1
0
P13
Auxiliary input 3 activation method
Same as auxiliary input 1
0
P14
Auxiliary input 4 activation method
Same as auxiliary input 1
0
P15
Auxiliary output 1 function
0: Output disabled
1: Engine running
2: Panel is in auto or test mode
3: Yellow alarm
4: Red alarm
5: Common alarm
6: Horn
7: Panel is in manual, auto or test mode
8: Panel is in auto mode
9: 6 sec stop output during engine stop
10: Fuel solenoid output
11: Auxiliary services
0
P16
Auxiliary output 2 function
Same as auxiliary output 1
0
P17
Auxiliary output 3 function
Same as auxiliary output 1
0
P18
Auxiliary output 1 activation method
0: De-Energize
1: Energize
1
P19
Auxiliary output 2 activation method
Same as auxiliary output 1
1
P20
Auxiliary output 3 activation method
Same as auxiliary output 1
1
P21
Test Mode
0: Test off load
1: Test on load
0
P22
Max. Stop solenoid working time
1-180 sec
6 sec