background image

EN-KO Electronic Control Systems                                                                                                      

AMF 4.0/ENG/K.K./02

 

 

18

started  in  auto  mode.  Mains  failure  delay  is  waited  before 
mains failure. 

P38  Generator under voltage failure  If  generator  voltage  fall  below  this  limit  under  over  voltage 

alarm occur. Failure occurred after  generator voltage failure 
delay 

P39  Generator over voltage failure 

If  generator  voltage  exceeds  this  limit  under  over  voltage 
alarm occur. Failure occurred after  generator voltage failure 
delay 

P40  Generator 

under 

frequency 

failure 

If generator frequency fall below this limit under over speed 
alarm  occur.  Failure  occurred  after  generator  frequency 
failure delay 

P41  Generator 

over 

frequency 

failure 

If  generator  frequency  exceeds  this  limit  under  over  speed 
alarm  occur.  Failure  occurred  after  generator  frequency 
failure delay 
 

P42  Last 10 failure 

Last ten alarm is recorded in the panel memory. There alarm 
can be controlled by this parameter. 

P43  Return to operator factory 

defaults 

When you select “YES” and press menu key operator 
parameters is returned to factory defaults 

 

Technician Parameters 

 

P44  Technician menu password 

Technician password can be changed by this parameter 

P45  Analog oil sender type 

Analog  oil  pressure  sender  type  can  be  selected  from  this 
parameter.  If  genset  has  only  digital  oil  switch,  and  this 
parameter is adjusted to “0” oil switch input is transferred to 
analog oil pressure sender input.  

P46  Oil switch type 

Oil pressure switch type can be selected from this parameter. 

P47  Low oil pressure failure 

If oil pressure fall below this limit. Oil pressure failure alarm 
is activated. 

P48  Analog 

temperature 

sender 

type 

Analog coolant temperature sender can be selected from this 
parameter.  If  genset  has  only  digital  coolant  temperature 
switch,  and  this  parameter  is  adjusted  to  “0”  coolant 
temperature switch input is transferred to analog temperature 
sender input. 

P49  Digital temperature switch type  Analog coolant temperature sender can be selected from this 

parameter. 

P50  Analog Oil pressure usage 

If analog sender is used for display purposes only. Generator 
doesn’t control this analog value. Value read from sender is 
used  only  for  display  purposes.  No  sensor  alarm  is  given  if 
sensor cable breaks. 

P51  Analog 

temperature 

sensor 

usage 

If analog sender is used for display purposes only. Generator 
doesn’t control this analog value. Value read from sender is 
used  only  for  display  purposes.  No  sensor  alarm  is  given  if 
sensor cable breaks. 

P52  Fueling system 

Fueling  system  is  can  be  adjusted  as  operating  or  stop 
solenoid.  When  this  parameter  is  selected  as  ECU  type. 
Cranking  output  behaves  like  start  output  and  fuel  solenoid 
output  behaves  like  stop  output.  This  configuration  is 
necessary in some type of ECU managed engines. In engine 
starting  condition,  start  output  is  activated  for  3  second  and 
cranking is stopped by means of activating stop output for 2 

Summary of Contents for AMF 4.0

Page 1: ...ature and engine hour Generator is monitored constantly and when generator or mains values exceed the limits adjusted in the parameter menu necessary actions are taken and alarm is activated Last ten alarms are recorded in the device memory All operating modes and timings can be adjusted in the parameter menu This flexibility is provided for different kinds of generator applications FUNCTIONS Manu...

Page 2: ...h temperature failure Charge fail warning Low oil pressure failure Periodic service time warning Auxiliary failure AMF 4 0 CONNECTION DIAGRAM AMF 4 0 Generator Contactor Relay Mains Contactor Relay G R S T N U V W N LOAD R S T N GENERATOR MAINS 12 23 19 18 17 22 11 14 35 34 33 32 31 30 29 28 27 26 25 24 Configurable Input 1 Default Oil Pressure Switch Configurable Input 3 Battery 1 2 Oil Pressure ...

Page 3: ...crank or preset cranking time when you press button Start button can be used in manual mode and when engine is not running Panel will display Str message during cranking Stop Button This button is used to stop the genset When you pressed this button first time panel switched to manual mode and if generator contactor is used before genset is switched to cooling mode If you pressed second time gense...

Page 4: ...ilure level to maximum oil press sender level Display Leds These leds are in the right side of numerical displays Leds indicates meaning of the value in the displays Values in the displays can be changed by up down and menu buttons Measuring Mode Button 8 The button selects the displayed values at lower 2 numerical display These displays can show generator voltage and frequency or mains voltage an...

Page 5: ...ons 9 These are manual hand mark automatic A letter and test buttons These buttons set running mode of genset There is mode indication leds near each of these buttons When panel is in off mode you can press these buttons to wake up panel and genset will run in selected mode REAR CONNECTIONS I T I S I R I R I T I S 30 31 32 33 34 35 22 23 24 25 26 27 28 29 G 11 12 13 14 15 16 17 18 19 20 21 CRANKIN...

Page 6: ... Cont NO Output terminal of generator contactor relay This output is connected to generator contactor 15 Charge Fail Excit Warning lamp output of charge alternator must be connected here In the cranking excitation current is supplied to charge alternator over 150 ohm resistor 16 Aux Input 1 Multiple function auxiliary input These inputs are activated if it is connected to battery negative If oil s...

Page 7: ...ator line and neutral are connected to these terminals 30 31 32 33 34 35 Current Transformer Inputs Secondary side of current transformer must be connected here Each transformer must be connected separately Note Battery negative must be connected to earth RUNNING MODES Automatic Mode If you press automatic button marked A genset will switch to automatic mode In this mode panel controls mains volta...

Page 8: ...gnals is detected Panel detects engine is running crank disconnects and switch to engine stabilization time Generator status led starts to blink During cranking Str message is shown in the display Oil pressure can rise before engine running so when oil pressure is detected crank disconnected after crank disconnect oil pressure delay 4 Stabilization After generator running signals detected panel wa...

Page 9: ...his alarm occurs that means panel couldn t start or stop engine All engine signals must be absent and engine must be still before cranking If one of the engine signals is detected before cranking panel switch to start and stop alarm Panel will show which signal is detected with engine start stop alarm If oil pressure signal is detected before cranking panel will wait for it to decrease to zero If ...

Page 10: ...ssword to these sections and enter to these sections by its passwords In parameter section leftmost digit starts to blink If you press up and down buttons you can increase and decrease the value shown in the blinking digit If you want to proceed to digit at one step right menu button must be pressed You can adjust this digit up and down buttons and then you press menu button again If you are in th...

Page 11: ... 9 Mains available 10 Emergency stop 11 Cabinet thermostat alarm 6 P8 Auxiliary input 2 function Same as auxiliary input 1 0 P9 Auxiliary input 3 function Same as auxiliary input 1 10 P10 Auxiliary input 4 function Same as auxiliary input 1 4 P11 Auxiliary input 1 activation method 0 Close to activate 1 Open to activate 0 P12 Auxiliary input 2 activation method Same as auxiliary input 1 0 P13 Auxi...

Page 12: ...password 0 999 060 P45 Analog Oil sender type 0 Analog oil sender disabled 1 Analog Endiksan type 2 Analog Olcusan VDO 7 Bar type 3 Analog Olcusan VDO 10 Bar type 4 Analog Olcusan VDO 80 PSI type 5 Analog VDO 5 Bar 6 Analog AKSA type 6 P46 Oil switch type 0 Oil switch disabled 1 Normally closed for low pressure 2 Normally open for low pressure 0 P47 Low oil pressure level 0 1 9 5 bar 1 2 bar P48 A...

Page 13: ... 9 99 0 87 P80 Generator Vs gain 0 01 9 99 0 87 P81 Generator Vt gain 0 01 9 99 0 87 P82 Generator Ir gain 0 01 9 99 3 53 P83 Generator Is gain 0 01 9 99 3 53 P84 Generator It gain 0 01 9 99 3 53 P85 Battery Voltage gain 0 01 9 99 0 54 P86 Mains Vr offset 29 29 V 0 P87 Mains Vs offset 29 29 V 0 P88 Mains Vt offset 29 29 V 0 P89 Generator Vr offset 29 29 V 0 P90 Generator Vs offset 29 29 V 0 P91 Ge...

Page 14: ...8 2 P62 100 P63 1 P64 98 25 P48 2 P62 100 P63 1 P64 99 26 P48 2 P62 125 P63 1 P64 103 27 P48 2 P62 150 P63 1 P64 144 28 P15 1 P62 100 P53 0 P45 3 P64 17 P48 2 P67 9 P52 1 P68 15 29 P15 1 P62 100 P53 0 P45 3 P64 23 P48 2 P67 9 P52 1 P68 15 30 P15 1 P62 100 P53 0 P45 3 P64 48 P9 10 P48 2 P67 9 P52 1 P68 15 31 P15 1 P62 100 P45 6 P64 51 P48 2 P68 15 P52 1 P67 9 32 P15 1 P62 100 P45 6 P64 65 P48 2 P68...

Page 15: ...ameter selected 1 panel will perform preheating for Preheat time P7 Auxiliary input 1 function It selects function of auxiliary input Auxiliary input can be adjusted as red or yellow alarm Activation time can be always active active from engine starting or active from engine stabilization time When input activates auxiliary input led lit and A1 A2 A3 or A4 message is shown according to activated a...

Page 16: ...Same as auxiliary input 1 P14 Auxiliary input 4 activation method Same as auxiliary input 1 P15 Auxiliary output 1 function This parameter select the functions of auxiliary output 1 Engine running If engine running signal generator voltage frequency or charge alternator warning lamb voltage is detected this output will be activated Panel is in auto or test mode If panel is in automatic or test mod...

Page 17: ...oad transferred to mains P27 Preheat time This parameter defines in automatic preheating how long preheating continues P28 Generator voltage failure delay When generator voltages are out of voltage limits a voltage alarm is given after generator voltage failure delay P29 Generator frequency failure delay When generator frequency is out of frequency limits high low speed alarm is given after genera...

Page 18: ...h input is transferred to analog oil pressure sender input P46 Oil switch type Oil pressure switch type can be selected from this parameter P47 Low oil pressure failure If oil pressure fall below this limit Oil pressure failure alarm is activated P48 Analog temperature sender type Analog coolant temperature sender can be selected from this parameter If genset has only digital coolant temperature s...

Page 19: ...ed all engine running signals absent panel will wait an additional protection delay This is necessary for engine to stop completely before next engine start Do not decrease this value if not necessary P62 Current transformer primary This parameter contains current transformer primary value If Current transformer primary is more than 999 you must change parameter menu current multiplier to x10 mode...

Page 20: ...gain calibration P84 Generator It gain Generator line T current gain calibration P85 Battery Voltage gain Battery voltage gain calibration P86 Mains Vr offset Mains line R voltage offset calibration P87 Mains Vs offset Mains line S voltage offset calibration P88 Mains Vt offset Mains line T voltage offset calibration P89 Generator Vr offset Generator line R voltage offset calibration P90 Generator...

Page 21: ...50VAC 10 A Voltage measurement 20 300VAC Frequency measurement 1 99 Hz Current measurements 5 A current inputs current transformer should be used Connection Screw socket Measurement Accuracy Phase voltages 2 Frequency 0 1Hz Phase currents 2 Charge Excitation Current 80mA 12VDC 160mA 24VDC Housing PPO Polyphenylene oxide 30 Glass Fiber Protection Class IP 52 Front side Weight 600 gr aprox Dimension...

Page 22: ...EN KO Electronic Control Systems AMF 4 0 ENG K K 02 22 Dimensions in mm Specifications are subject to change without notice ...