INSTALLATION AND CONNECTION
smart Econ - emz-HCW - 180116
51
smart Econ Room controller
Node number room controller
A multi-digit number is glued on the packaging, on the back of the housing and on the terminal
inside.This is the CAN account number, a unique, unmistakable number, similar to a serial number.
One room controller can be installed per heating circuit in a system.
Each room controller has an individual node number and must be logged into the controller as a bus
device by entering this number, see “Configuring the room controller ›CONFIG RC‹” on page 123.
Make a note of the node numbers!
Dimensions room controller
Opening the room controller housing
First remove the hand wheel, then remove the cover at each corner until the snap lock is
unlocked.To assemble, proceed in reverse order.
Installation location room controller
• As a heating circuit remote control in a reference room.
• As an individual room controller in the respective room.
• Usual installation height: approx. 130 to 140 cm above the top edge of the finished floor.
• Never expose a smart Econ room controller to other heat sources.
Ensure that the installation site is draft-free.
External heat sources could be, for example, direct sunlight, heat generated by electric equip-
ment, heat radiating from lights (halogen spotlights!), heated walls or radiators near the system,
etc.
• Install smart Econ room controllers in a freely accessible place to ensure that its regulatory func-
tions work properly.
Dimensions in mm