DEVICE CONFIGURATION
smart Econ - emz-HCW - 180116
133
This value multiplied by the setpoint deviation in the room results in a change in the flow tem-
perature.
Example: It's 3 degrees too cold in the room.The room temperature influence factor = 2.
→
The flow temperature is increased by 3 * 2 = 6 degrees.
›room influence limit (K)‹: Maximum limitation for increasing the flow temperature (K)
Configuring the mixer control (heating circuits with mixer)
• For example, select ›MIXER HEAT CIRC. 2‹ in the ›HEAT CIRCUIT 2‹ menu.
(Example, depending on the selected system)
Note:
Mixer circuits are always preset for underfloor heating!
• Change the parameters if necessary.
→
Page 132
MIXER HEAT CIRC. 2
^
current set point (°C)
0
shift heating curve
0.0
minimum supply temp. (°C)
20
maximum supply temp. (°C)
50
set point at <1>°:
36
set point at <2>°:
34
set point at <3>°:
31
set point at <4>°:
22
i
interval (sec)
30
Amplification (0.1Sec/K)
20
MIXER HEAT CIRC. 2
^
gain room influence
2
room influence limit (K)
10
economy mode
0
activated:
YES
BACK
i