background image

12427-5-0806

Page 10

SERVICE AND MAINTENANCE SUGGESTIONS

CALL SERVICEMAN

GENERAL: 

All furnaces have been fire-tested to check for proper op-

eration. This includes, main burner flame, pilot flame, fan operation, fan 
control, limit control and automatic valve operation. If the furnace fails to 

function on initial installation, it is advisable to re-check the following: 

1. 115 volts to the junction box.

2. Inlet gas pressure.

3. The 24 volt system.

4. Type of gas being used and that shown on the rating label.

The Service Department at Empire Comfort Systems, Inc. may be contacted 

to assist in servicing furnace.

Standing Pilot Model

Servicing the Pilot and Main Burners, Pilot Orifice, Thermocouple, 

and Main Burner Orifices: 

Disconnect the gas supply at the inlet to the 

control valve. Then remove the burner door to gain access to the above 

listed components.

Spark Igniter Does Not Light Pilot: 

With air in the gas line, such as when 

the furnace is first installed or was off all summer, the pilot flame may 

be too lean to ignite on the first few trials. Turn the control valve knob to 

pilot position and depress the red reset button. Holding the button down 

continually to bleed the line;.

1.  Use lighter rod to light pilot with a match.

2.  Use the piezo ignitor at 30 second intervals until it lights.

If Electrode Does Not Produce Spark:

1.  Check wire connections.

2.  Check gap for pilot burner to the electrode tip. Should be between 

1/8" (3mm) and 3/16" (5mm). Electrode wire and tip must be more 

than 1/4" (6mm) away from all other metal components.

If Pilot Does Not Light By Any Means:

1.  Check valve knob for being in the "Pilot" position.

2.  Check  pilot  adjustment  for  being  full  open  (counterclockwise  to 

open).

3.  If gas is available in the supply tubing, the pilot orifice and/or pilot 

burner is probably restricted by a spider web. Clean pilot assembly 

and relight.

If Pilot Does Not Remain On After Releasing Knob: 

1.  Follow instructions and hold button down longer and harder.

2.  Determine if pilot flame extends past thermocouple; if not, adjust 

input or clean pilot burner.

3.  Replace thermocouple if millivolts read less than 15 millivolts. 

Main Gas Valve Does Not Open When Thermostat Is Turned To On:

1.  Check for 24 volts to valve by removing one wire and touching to the 

SAME TERMINAL 

it was on. Terminal should have a light spark. 

DO NOT SHORT ACROSS TERMINALS, AS IT WILL BURN 

OUT THE WALL THERMOSTAT.

2.  Thermostat wires at the wall may be shorted, so check for a faulty 

thermostat.

3.  To check for line voltage to furnace, remove front panel and short 

across two-terminal fan control to allow fan to operate (Figure 14).

CAUTION:

 Label all wires prior to disconnection when servicing 

controls. Wiring errors can cause improper and dangerous operation. 

Verify proper operation after servicing.

IP-Model Pilot

This heater is using a Honeywell "Smart Valve" system for intermittent 

pilot ignition.
On a call for heat by the thermostat this control turns on a 24 volt mini 

hot surface ignitor which lights a pilot that in turn lights the main burner. 

The gas valve used in this system is a step opening which opens at a 

lower pressure for ignition and then steps to a full inlet pressure of 4" H

2

pressure on Natural gas and 10" H

2

0 pressure on LP gas.

Pilot Flame Adjustment

The pilot flame should envelop 3/8 to 1/2 inch (10 to 13mm) of the tip 

of the flame rod. See Figure 10.
To adjust:

1.  Remove the pilot adjustment cover screw.

2.  Turn the inner adjustment screw clockwise 

to decrease 

or counterclockwise 

 

to increase pilot flame. Pilot adjust-

ment is shipped at full flow rate. Turn the inner adjustment screw 

clockwise

 if the inlet pressure is too high.

3.  Replace the cover screw after the adjustment to prevent gas leak-

age.

ON

OFF

IGNITOR

CONTROL

INLET PRESSURE TAP

OUTLET PRESSURE TAP

PILOT ADJ USTMENT-�

UNDER CAP SCREW

PILOT OUTLET

PRESSURE REGULATOR�

ADJ USTMENT-UNDER CAP�

SCREW

GAS FLOW

IGNITOR

CONTROL

TO 24 V. THERMOSTAT

TO 24 V. COMMON ON TRANSFORMER

TO 24 V."HOT" ON TRANSFORMER

WIRING

I P-MODEL GAS  VALVE AND WIRING

IGNITOR-PILOT ASSY.

FAN�

SWITCH

MOTOR

HONEYWELL IP�

SMART VALVE

120 VAC

LIMIT�

CONTROL

VENT SAFETY�

LIMIT

THERMOSTAT

40 VA TRANSFORMER

24 VAC

120VAC

VALVE CONTROL�

CONNECTOR

L1 "HOT"

L2 NEUTRAL

LADDER WIRING DIAGRAM-IP VALVE

Figure 15

Summary of Contents for AW-40-1SPP

Page 1: ...not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire depa...

Page 2: ...amaged parts DO make a periodic visual check of pilot and burners Clean and replace damaged parts CAUTION Pilot hole covermust be kept tightly closed during operation DO NOT use this heater if any part has been under water Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water This furnace mu...

Page 3: ...o light pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new ta...

Page 4: ...ll Ducts must have the same cross sectional area as the free area of the openings to which they connect The minimum dimension of air ducts must not be less than 3 inches Installation in an Unconfined Space An unconfined space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1 000 Btuh of the combined total input rates of all appliances which draw com...

Page 5: ...ischarge registers SOR 1 or SOK 1 the furnace cannot be recessed into the wall 5 Clearance to sidewall or combustible material is 4 inches 10 2cm 6 Ceiling clearance is 4 inches 10 2cm 7 Floor and rear wall clearance is 0 zero inches 0mm 8 Clearance of 18 inches 46cm is required to adjacent wall or combustible material when flush mounted SOR 1 side outlet register is used Before Installing Consider...

Page 6: ... 3 8 x 9 3 8 238mm x 238mm side outlet wall plate over outer boot pass the outer boot through the wall and attach side wall plate to furnace side of wall with 2 10 x 1 1 2 38mm provided screws 5 Attach outer boot to the cabinet side with 4 8 x 1 4 6mm provided screws 6 Position and attach inner boot to inner shield with 4 8 x 1 4 6mm provided screws 7 Placetheregisteroverthe63 4 171mm squareopenin...

Page 7: ... on the wall which is behind the furnace Attach furnace to wall at the outer casing top with 2 toggle bolts provided and to floor at the outer casing bottom with 2 10 x 1 1 2 38mm screws provided Gas Supply Check all local codes for requirements especially for the size and type of gas supply line required On Natural gas lines less than 75 22 9m long use 1 2 13mm pipe on longer runs use 3 4 19mm iro...

Page 8: ...he pilot faster than the piezo under this condition Proper Pilot Flame The correct pilot flame Figure 10 will be blue extending past the thermocouple The flame will surround the thermocouple just below the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remove the pilot cover screw on the control valve Figure 9 and turn the adjustment screw clockwise to r...

Page 9: ... Outside Wall Insulated Vent Enclosure Vented wall furnaces installed in buildings with flat roofs can have poor venting The cold vent pipe will have a delay in proper venting and cause the wall furnace to shut OFF by the vent safety switch To prevent delayed venting as well as condensation of flue products an insulated vent enclosure is recommended Use type B vent pipe and maintain at least a one i...

Page 10: ...st input or clean pilot burner 3 Replace thermocouple if millivolts read less than 15 millivolts Main Gas Valve Does Not Open When Thermostat Is Turned To On 1 Check for 24 volts to valve by removing one wire and touching to the SAME TERMINAL it was on Terminal should have a light spark DO NOT SHORT ACROSS TERMINALS AS IT WILL BURN OUT THE WALL THERMOSTAT 2 Thermostat wires at the wall may be shor...

Page 11: ...Push in gas control knob slightly and turn clockwise to OFF Do not force 5 Replace control access panel lower front panel LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 Remove control access panel lower front panel 5 Turn gas control knob clockwise to OFF 6 Wait ten 10 minutes to clear out any g...

Page 12: ...ace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand ON OFF IGNITOR CONTROL GAS FLOW GAS VALVE SHOWN IN OFF POSITION...

Page 13: ...ot Valve Ignition OFF Wait for Flame Signal to Disappear Pilot Valve Closes Ignition OFF Main Pilot Valves Close Flame Lost More Than 5 Times in One Call for Heat 5 Minute Retry Delay 3 Second Flame Recycle Delay YES NO NO YES NO YES YES NO YES NO 1 Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame has not lit It will turn back ON for the final 30 seconds of the...

Page 14: ...Gas is Flowing Wait to Assure Pilot Gas Tubing is Purged Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control Must Measure at Least 19 5 VAC with Igniter Powered See Inset A to Identify Proper Lead This Check Must be Done with the SmartValve Control Connected and Igniter Powered Replace Igniter Flame Rod Assembly Check that Pilot Flame Makes Good Contact with Pilot Burner Fla...

Page 15: ...PG ONLY 45 R 3031 BURNER 3 REQUIRED 46 DV 1239 BURNER BRACKET 47 UH 452 TRANSFORMER MOUNTING BRACKET IP ONLY 47 UH 810 TRANSFORMER MOUNTING BRACKET SPP ONLY 48 R 1995 TRANSFORMER SPP ONLY 48 8720100 TRANSFORMER IP ONLY 49 UH 451 JUNCTION BOX COVER 50 DV 572 JUNCTION BOX 51 DV 1260 COVER PLATE AIR DROP 52 872056 BUSHING 53 872053 CORD SET 54 8720148 BUSHING 55 DV 1215 BOTTOM PLATE 56 R 3034 PILOT N...

Page 16: ...12427 5 0806 Page 16 ...

Page 17: ...12427 5 0806 Page 17 Service Notes ...

Page 18: ...8 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623 PH 1 618 233 7420 PH 1 800 851 3153 FAX 1 618 233 7097 FAX 1 800 443 8648 E MAIL info empirecomfort com WEB SITE www empirecomfort com ...

Reviews: