background image

12427-5-0806

Page 8

Attention! 

If one of the above procedures results in pressures in excess 

of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, it will result 

in a hazardous condition.

Checking Manifold Pressure

Both Propane and Natural gas valves have a built-in pressure regulator 

in the gas valve. Natural gas models will have a manifold pressure of 

approximately 4.0" w.c. (.996kPa) at the valve outlet with the inlet pressure 

to the valve from a minimum of 5.0" w.c. (1.24kPa) for the purpose of 

input adjustment to a maximum of 10.5" w.c. (2.615kPa). Propane gas 

models will have a manifold pressure approximately 10.0" w.c. (2.49kPa) 

at the valve outlet with the inlet pressure to the valve from a minimum of 

11.0" w.c. (2.739kPa) for the purpose of input adjustment to a maximum 

of 13.0" w.c. (3.237kPa). 
A 1/8" (3mm) N.P.T. plugged tapping, accessible for test gauge connection, 

is located on the outlet side of the gas control.
The built-in regulator comes on at approximately 1/4th pressure and full 

on in 10 seconds.

Figure 9

High Altitudes

For altitudes/elevations above 2,000 feet (610m), input ratings should 

be reduced at the rate of 4 percent for each 1,000 feet (305m) above sea 

level. For Canadian high altitude applications, this appliance is suitable 

for installation at elevations between 0 feet (0m) and 4,500 feet (1,372m) 

without change. 

Piezo Pilot Ignitor Instructions

Depressing  the  red  button  completely  causes  a  spark  to  occur  at  the 

pilot. This is a substitute for a match which requires opening the pilot 

hole cover.
To light the pilot, it is important that the electrode be 1/8" (3mm) from 

the thermocouple. The spark must occur at the point the burner flame 

hits the thermocouple. The end of the electrode will be red hot with the 

pilot on.
On a new installation with air in the gas line, it is suggested that a match 

be used. The match will light the pilot faster than the piezo under this 

condition. 

Proper Pilot Flame

The  correct  pilot  flame  (Figure  10)  will  be  blue,  extending  past  the 

thermocouple.  The  flame  will  surround  the  thermocouple  just  below 

the tip.
Natural gas pilots require adjusting when the inlet gas pressure is above 

5" w.c. (1.245kPa). Remove the pilot cover screw on the control valve 

(Figure 9), and turn the adjustment screw clockwise to reduce flame. 

Replace pilot cover screw to eliminate gas leakage.
LP gas (propane) will not require adjustment.
After use, cleaning may be required for the proper flame.

Proper Main Burner Flame

The correct flame will be a short, blue inner flame with a much larger, 

light blue, outer flame. The burner does not have a primary air adjustment. 

The flame will be correct if the factory-set pressure and orifice opening 

are used. After the furnace has been operating, the burner ports may 

be blocked by foreign matter carried in by combustion air. Therefore, 

cleaning of the burner may be needed for proper flame.
To clean burner port disconnect the gas supply to the valve, and remove 

the screws fastening the burner door. After removing the burner door  

from the burner box, remove each main burner. Pilot mounting bracket 

will need to be unscrewed and moved out of the way to remove all burners. 

Burners can be blown out using compressed air or by blowing through 

them. Be sure there is no lint or foreign debris blocking the burner ports. 

Reassemble using the same screws earlier removed and locate pilot in 

the same position as before and noted above.

SPARK�

ELECTRODE

THERMOCOUPLE

PILOT

BURNER

STANDING PILOT

PILOT LOCATION END VIEW

PILOT SHIELD

THERMOCOUPLE

SPARK�

ELECTRODE

STANDING PILOT SHOWN

BURNER

PILOT

HOT SURFACE�

IGNITOR

FLAME�

ROD

GROUND�

ELECTRODE

3/8" TO 1/2"�

PILOT FLAME

IP-MODEL PILOT

 

Figure 10

Figure 11

Cleaning Combustion (Exchanger) Assembly

A  QUALIFIED  SERVICE  PERSON  should  remove  the  combustion 

(exchanger) assembly and flue baffles. Apply air pressure to the inside 

of the combustion (exchanger) assembly and flue baffles in order to clear 

all passageways.

Summary of Contents for AW-40-1SPP

Page 1: ...not store or use gasoline or other flam mable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas sup plier s instructions If you cannot reach your gas supplier call the fire depa...

Page 2: ...amaged parts DO make a periodic visual check of pilot and burners Clean and replace damaged parts CAUTION Pilot hole covermust be kept tightly closed during operation DO NOT use this heater if any part has been under water Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water This furnace mu...

Page 3: ...o light pilot lights perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on walls of new cylinders and tanks is possible Therefore people should be particularly alert and careful when new tanks or cylinders are placed in service Odor fade can occur in new ta...

Page 4: ...ll Ducts must have the same cross sectional area as the free area of the openings to which they connect The minimum dimension of air ducts must not be less than 3 inches Installation in an Unconfined Space An unconfined space is an area including all rooms not separated by doors with a volume greater than 50 cubic feet per 1 000 Btuh of the combined total input rates of all appliances which draw com...

Page 5: ...ischarge registers SOR 1 or SOK 1 the furnace cannot be recessed into the wall 5 Clearance to sidewall or combustible material is 4 inches 10 2cm 6 Ceiling clearance is 4 inches 10 2cm 7 Floor and rear wall clearance is 0 zero inches 0mm 8 Clearance of 18 inches 46cm is required to adjacent wall or combustible material when flush mounted SOR 1 side outlet register is used Before Installing Consider...

Page 6: ... 3 8 x 9 3 8 238mm x 238mm side outlet wall plate over outer boot pass the outer boot through the wall and attach side wall plate to furnace side of wall with 2 10 x 1 1 2 38mm provided screws 5 Attach outer boot to the cabinet side with 4 8 x 1 4 6mm provided screws 6 Position and attach inner boot to inner shield with 4 8 x 1 4 6mm provided screws 7 Placetheregisteroverthe63 4 171mm squareopenin...

Page 7: ... on the wall which is behind the furnace Attach furnace to wall at the outer casing top with 2 toggle bolts provided and to floor at the outer casing bottom with 2 10 x 1 1 2 38mm screws provided Gas Supply Check all local codes for requirements especially for the size and type of gas supply line required On Natural gas lines less than 75 22 9m long use 1 2 13mm pipe on longer runs use 3 4 19mm iro...

Page 8: ...he pilot faster than the piezo under this condition Proper Pilot Flame The correct pilot flame Figure 10 will be blue extending past the thermocouple The flame will surround the thermocouple just below the tip Natural gas pilots require adjusting when the inlet gas pressure is above 5 w c 1 245kPa Remove the pilot cover screw on the control valve Figure 9 and turn the adjustment screw clockwise to r...

Page 9: ... Outside Wall Insulated Vent Enclosure Vented wall furnaces installed in buildings with flat roofs can have poor venting The cold vent pipe will have a delay in proper venting and cause the wall furnace to shut OFF by the vent safety switch To prevent delayed venting as well as condensation of flue products an insulated vent enclosure is recommended Use type B vent pipe and maintain at least a one i...

Page 10: ...st input or clean pilot burner 3 Replace thermocouple if millivolts read less than 15 millivolts Main Gas Valve Does Not Open When Thermostat Is Turned To On 1 Check for 24 volts to valve by removing one wire and touching to the SAME TERMINAL it was on Terminal should have a light spark DO NOT SHORT ACROSS TERMINALS AS IT WILL BURN OUT THE WALL THERMOSTAT 2 Thermostat wires at the wall may be shor...

Page 11: ...Push in gas control knob slightly and turn clockwise to OFF Do not force 5 Replace control access panel lower front panel LIGHTING INSTRUCTIONS 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 Remove control access panel lower front panel 5 Turn gas control knob clockwise to OFF 6 Wait ten 10 minutes to clear out any g...

Page 12: ...ace any part of the control system and any gas control which has been under water 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand ON OFF IGNITOR CONTROL GAS FLOW GAS VALVE SHOWN IN OFF POSITION...

Page 13: ...ot Valve Ignition OFF Wait for Flame Signal to Disappear Pilot Valve Closes Ignition OFF Main Pilot Valves Close Flame Lost More Than 5 Times in One Call for Heat 5 Minute Retry Delay 3 Second Flame Recycle Delay YES NO NO YES NO YES YES NO YES NO 1 Ignitor will turn OFF about 30 seconds into the trial for ignition if the pilot flame has not lit It will turn back ON for the final 30 seconds of the...

Page 14: ...Gas is Flowing Wait to Assure Pilot Gas Tubing is Purged Measure Voltage Between 24V Hot and 24V Common Leads to SmartValve Control Must Measure at Least 19 5 VAC with Igniter Powered See Inset A to Identify Proper Lead This Check Must be Done with the SmartValve Control Connected and Igniter Powered Replace Igniter Flame Rod Assembly Check that Pilot Flame Makes Good Contact with Pilot Burner Fla...

Page 15: ...PG ONLY 45 R 3031 BURNER 3 REQUIRED 46 DV 1239 BURNER BRACKET 47 UH 452 TRANSFORMER MOUNTING BRACKET IP ONLY 47 UH 810 TRANSFORMER MOUNTING BRACKET SPP ONLY 48 R 1995 TRANSFORMER SPP ONLY 48 8720100 TRANSFORMER IP ONLY 49 UH 451 JUNCTION BOX COVER 50 DV 572 JUNCTION BOX 51 DV 1260 COVER PLATE AIR DROP 52 872056 BUSHING 53 872053 CORD SET 54 8720148 BUSHING 55 DV 1215 BOTTOM PLATE 56 R 3034 PILOT N...

Page 16: ...12427 5 0806 Page 16 ...

Page 17: ...12427 5 0806 Page 17 Service Notes ...

Page 18: ...8 Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 2623 PH 1 618 233 7420 PH 1 800 851 3153 FAX 1 618 233 7097 FAX 1 800 443 8648 E MAIL info empirecomfort com WEB SITE www empirecomfort com ...

Reviews: