background image

12434-7-0706

Page 17

Cleaning

The blower wheel will collect lint and could require cleaning once 

a year.  If the air output decreases or the noise level increases,  

it indicates a dirty wheel.  Complete removal of the wheel and 

scrubbing it with a brush under flowing water is recommended.
Oiling

The blower motor has an oil hole located on each end of the motor.  

Use #20 motor oil only.  It is best to oil the motor several times 

during the heating season using 2 or 3 drops each time.  If the motor 

fails to start and hums, it could be a tight bearing due to lack of 

oil.  This may be corrected by pouring kerosene in the oil holes, 

allowing to stand for a few hours and then oiling properly.

1

2

3

4

5

6 7

8

9

10

11

12

PARTS LIST

Index 

No.

Part

No.

Description

1

R-2090

Motor

2

632016

Motor Cushion

 3

RH-036

Motor Support

4

642030

Blower Wheel

5

RH-710

Blower Housing Assembly

6

9120106

Fan Control Switch

7

872087

Heyco Bushing

8

DV-806

Switch Box

9

DV-807

Switch Box Cover

10

R-2091

Wire Assembly 19" (483mm)

11

8720161

Heyco Bushing

12

R-2099

Cord Set 72" (1.83m)

OPTIONAL BLOWER INSTALLATION INSTRUCTIONS (continued)

Summary of Contents for DV-25-2SG

Page 1: ...onvertible for use with other gases unless a certi ed kit is used Installer Leave these instructions with the consumer Consumer Retain these instructions for future use Donotstoreorusegasolineorother...

Page 2: ...ations 6 Gas Supply 7 Clearances 8 Installation Instructions 8 10 Thermostat Location 10 Lighting Instructions 11 Pilot Flame Characteristics 12 Main Burner Flame Characteristics 12 Maintenance 13 Tro...

Page 3: ...n More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is imperative that control compartments burners and circulating air passageways of the appliance...

Page 4: ...s perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on w...

Page 5: ...iredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certi ed 3 SIGNAGE Ametalorplasticidenti cationplateshallbe permanently mounted to the exterior...

Page 6: ...ed so it is not subject to physical damage by a moving vehicle Quali ed Installing Agency Installationandreplacementofgaspiping gasutilizationequipment or accessories and repair and servicing of equip...

Page 7: ...o aid in servicing It is required by the National Fuel Gas Code that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that i...

Page 8: ...gulator malfunction the six 6 1 83m feet distance will reduce the chance of gas entering the vent cap Location of Furnace Pickalocationonanoutsidewallwithaclearspaceof28 711mm high by 49 124cm wide in...

Page 9: ...cap into the 4 102mm diameter ueoutlettube Attachventcaptooutside mounting plate with 3 10 x 1 2 13mm screws provided 4 Installation is completed Reassembly And Resealing Vent Air Intake System When...

Page 10: ...due to spiders System Check Figure 6 Amillivoltmeterisrequiredtocheckthesystem Millivoltreadings should be Across the thermopile terminals 400 450 millivolts with thermostat OFF Across the thermopile...

Page 11: ...clockwise to OFF Do not force 5 Replace casing front assembly 1 STOP Read the safety information above 2 Set the thermostat to lowest setting 3 Turn off all electric power to the appliance if appli ca...

Page 12: ...ng on the inner casing bottom On Propane gas if a whistling noise resonation occurs screw air adjustment bolt into the chamber support in order to reduce the amount of primary air If the whistling noi...

Page 13: ...s a See Page 12 Primary Air Adjustment b Reduce manifold pressure c Size main burner ori ce with a drill bit For DV 25 use 54 drill bit For DV 35 use 50 drill bit Removing Main Burner 1 Disconnect the...

Page 14: ...ifold 30 R 191 Manifold Union Assembly 31 R 5600 Gas Valve Nat 7000 MVRLC 31 R 5601 Gas Valve LP 7000 MVRLC 32 DV 1003 Valve Bracket 33 DV 764 Gasket Chamber Support DV 765 2 Each Required 34 DV 908 V...

Page 15: ...12434 7 0706 Page 15 PARTS VIEW...

Page 16: ...l from black hot wire on motor 4 Attach green ground wire beneath one of the 10 x 1 2 13mm screws on the blower housing Fan Control The automatic fan control is located in the switch box The switch bo...

Page 17: ...ng 2 or 3 drops each time If the motor fails to start and hums it could be a tight bearing due to lack of oil This may be corrected by pouring kerosene in the oil holes allowing to stand for a few hou...

Page 18: ...12434 7 0706 Page 18 SERVICE NOTES...

Page 19: ...12434 7 0706 Page 19 SERVICE NOTES...

Page 20: ...12434 7 0706 Page 20 Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 PH 618 233 7420 or 800 851 3153 FAX 618 233 7097 or 800 443 8648 info empirecomfort com www empirecomfort com...

Reviews: